27
ENG
“Wellness” +0300060EN - rel. 1.2 - 03.09.2012
installer
user
ser
vice
From the main screen press:
•
PRG to access the main menu,
•
DOWN to select the installer menu,
•
ENTER,
•
enter the password “77”,
•
ENTER to confi rm and access the installer menu.
Installer menu screens:
1. Regulation type
2. Utilities config.
3.Functional options
4. Drain options
5. Supervisory
6. GSM
To navigate inside the screens:
•
UP or DOWN to change the value (within the options/range),
•
ENTER to confi rm and move the cursor to the next value
•
ESC to return to the installer menu.
7.1 Type of control
Setting: type of control, type of signal, unit of measure, and in the
models with two cylinders, choice between “parallel sequence” or “series
sequence”.
Regolation Type (1/3)
parameter
options/range
description
Working mode
MODULATION
steam production modulating
STEP *
steam production step
Select
Regulation
ONE TEMPERATURE
PROBE
temperature control with one
probe
PROPORTIONAL
proportional control with signal
set from external controller
TWO TEMPERATURE
PROBE
temperature control with two
probes (With possibility of
adjustment on the average
between the two)
ON/OFF SIGNAL
adjustable thermostat
(Appears only if MODE STEP
FUNCTION)
Signal type
NTC (default)
4/20 mA
0/20 mA
0/10 V
2/10 V
0/1 V
Meas. unit
°C-kg/h (default)
°F - lb/hr
Regolation Type (2/3)
Probe confi guration
parameter
range
def.
U.M.
Min. scale
(not accessible in ON/OFF
control mode)
-100...(Max.scale)
0.0
°C/ °F
Max. scale
(not accessible in ON/OFF
control mode)
(Min.scale)...250
100.0
°C/ °F
Offset
-10.0...10.0
0.0
°C/ °F
Weight probe 1 ( only if
selected two probes )
0.... 100
50
%
Weight probe 2 (only if
selected two probes )
0.... 100
50
%
Regolation Type (3/3)
Regolation Parameter
parameter
range
default
U.M.
T Differential
1.0 …19.9
2.0
°C
Max. Production
20…100
100
%
7. INSTALLER MENU
7.2 Utilities confi guration
1. Essence
2. Fans
3. Sanification
4. Light
Essence 1 (1/3)
parameter
range
default
U.M.
Enable outpout
essence 1
YES/ NO
NO
Time On
0... 60
0
sec
Time Off
0... 999
0
sec
Name
NAME ESSENCE
ESSENCE 1
Essence 2 (2/3)
parameter
range
default
U.M.
Enable outpout
essence 2
YES/ NO
NO
Time On
0... 60
0
sec
Time Off
0... 999
0
sec
Name
NAME ESSENCE
ESSENCE 2
Essence 3 (3/3)
parameter
range
default
U.M.
Enable outpout
essence 3
YES/ NO
NO
Time On
0... 60
0
sec
Time Off
0... 999
0
sec
Name
NAME ESSENCE
ESSENCE 3
The essences are dispensed in steam bath when the humidifi er is in
production and the temperature reaches 70% of set point.
For example: 50 ° C set point with the essence will be provided when
the humidifi er is in production and the measured temperature exceeds
35 ° C.
Warning:
Make sure the pump is properly connected external
essences.
FANS (1/3)
parameter
range
default
U.M.
FAN SUPPLY
Enable fan
YES/ NO
NO
Mode
Man…Automatic...Programs
Manual
Type
Setpoint
Setpoint
Fan Threshold
0.0 ... 50.0
0.0
°C
Turn on delay
0...199
0
min
Turn off delay
0...199
0
min
In Manual mode, the on / off fan are activated manually by the mask “Rapid
Select”.
In AUTO mode and type setpoint, the fan is only active when you are in the
production of steam, with delays switched on or off , selectable. It ‘can set a
temperature threshold below which the fan is still active even though the
production of steam.
In AUTO mode and type PROGRAMS (active only if scheduler enabled), the fan
remains on during all sections of humidifi er ON and OFF switched off during
the scheduler. If the steam bath temperature is below the threshold, the fan
is not active ongi case.
FANS (2/3)
parameter
range
default
U.M.
EXTRACT FAN
Enable fan
YES/ NO
NO
Mode
Man…Automatic
Manual
Type
Setpoint...Periodic
Setpoint
T ON: T OFF:
0...199
0
min
Turn on delay
0...199
0
min
Turn off delay
0...199
0
min
In Manual mode, the on / off fan are activated manually by the “Rapid
Selection” screen.
In AUTO mode and type setpoint, the fan turns off when you are in the
production of steam, with delays switched on or off , selectable.