5. STARTING AND USER INTERFACE
Before starting the humidifi er, check:
water connections: Fig. 2.a page 10. In the event of water leaks do not
start the humidifi er before having resolved the problem;
steam distribution: Fig. 3.d page 13;
electrical connections chap. 4
5.1 Starting
1
1
0
ON
2
if the cylinder is new, run a pre-wash cycle (the cylinder is fi lled and
emptied three times, cleaning the inside walls from impurities, see
menu maintanance >change cylinder > fl ush new cylinder).
5.2 Stopping
1
empty the water in the cylinder to avoid stagnation: see manual
drain on “SET” screens).
2
1
0
O
FF
Note: the next restart, after a cylinder unloading, the following screen
appears:
If you replaced the cylinder is necessary
to reset the timer:
You want to do it now?
YES…NO…Remember the next
restart
Select YES only if the cylinder has been replaced (or cleaned in the case of
cylinders can be opened).
5.3 Basic confi guration (WIZARD)
Select language:
1. English
2. Italiano
3. Deutsch
4. Francais
5. Espaniol
Press DOWN to select the number corresponding to the desired language
and then ENTER to confi rm. This screen remains displayed for 60 seconds.
Subsequently, the following screen will be displayed:
Note: The language can also be changed by menu installer (Installer
menu> Function Optional 3/3 > language).
The language can also be changed by any form by pressing UP + ENTER
Help procedure for basic confi gurations.
Push ENTER to start or ESC to go back to language selection.
Regolation select. :
1 One Temperature probe
2. Two Temperature probes
3. Proportional signal
4. On/OFF contact
Press DOWN to select the number corresponding to the desired function
and then ENTER to confi rm. Press ESC repeatedly to return to the “Main”
screen.
Signal Type:
1. NTC probe
2. 0…1 Vdc
3. 2…10 Vdc
4. 0…10 Vdc
5. 0…20 mA
6. 4…20 mA
Press DOWN to select the number corresponding to the desired function
and then ENTER to confi rm. Press ESC repeatedly to return to the “Main”
screen.
Range probe signal (only for active
probes )
range
default U.M.
Min. Scale
-100....250
0
%rH
Max. SCale
-100...250
100
%rH
Weight probe 1 (only with 2
probes)
*
0....100
50
Weight probe 2 (only with 2
probes)
*
0....100
50
(*) to achieve a temperature value measured with two probes, the
humidifi er carries out the following calculation:
Tm= (Ts1*W1/100) + (Ts2*W2/100)
Tm= temperature shown on the display
Ts1 & Ts2= temperatures read by the two probes
W1 & W2= weights attributed to the two probes, percentage value
(W1+W2=100)
For example, with the following values:
Ts1= 42° W1= 60%
Ts2= 44° W2= 40%
Tm= (42*60/100) + (44*40/100)= 42.8 °C
Press DOWN to select the number corresponding to the desired function
and then ENTER to confi rm. Press ESC repeatedly to return to the “Main”
screen.
Function Modality:
1. Steam production modulating
2. Steam production step*
* STEP means that the humidifi er is on standby until the steam bath
temperature falls below the set diff erential mask Installer Menu> Type
Regolation (3/3)> T Diff erenz. (If type Regolation with Probe), then
activates 100% of maximum production set. If the regolation is made
with external thermostat, humidifi er remains idle until the thermostat
contact is open, you turn 100% of maximum production set when the
contact is closed.
Press DOWN to select the number corresponding to the desired
function and then ENTER to confi rm. Press ESC repeatedly to return to
the “Main” screen.
Please the jumper in elecrtonic board
Probe 1 JS5
Probe 2 JS6
Screen of visiualization position of jumpers JS5 and JS6 according to the
previously selected signal. ENTER to confi rm and continue, ESC to return
to previous form.
Choose whether or not to repeat the wizard for each power.
Do this Wizard again at next restart? YES/NO
•