Installation, Operating & Maintenance Manual
11
1.3.2 Water drain
The HumiSteam also requires connection to a drain. The drain water characteristics are:
The drain line can be 1-1/2” schedule 40 CPVC, 1-1/2” copper, or 1-1/2” Polypropylene. In all cases, the drain
tube is slipped over the drain outlet on the bottom of the humidifier. It is not glued or otherwise attached to the
humidifier, so it must be supported by itself.
Drain line must be installed and plumbed to an open drain immediately after the unit. For proper operation of
the unit, the open drain should be installed before the trap (if allowed by local code).
WARNING: Do NOT use PVC piping unless the unit has the optional drain tempering valve installed.
UE003 UE005
Drain rate per hour
2.2 gph
3.7 gph
Instant drain rate
1.3 gpm
Connection
1-1/2" nominal diameter
Typical temperature
212°F