CAREL
humiSteam Lite
22
2.2 The HumiControl Controller
The HumiSteam Lite uses an LED version of the HumiControl,
which communicates all information through 3 LEDs on the front
panel.
The
Green LED
to the left indicates the unit is powered.
The
Yellow LED
in the center indicates that the unit is producing
steam. If it glows solid, the unit is at full capacity, otherwise it
will flash, each flash indicating 1/10 of capacity, so that 8 flashes means 80% capacity.
The
Red LED
to the left indicates alarms. It indicates alarms by a series of long (1 per second) or short (2 per
second) flashes. See the Alarms section for a table.
Each time the humidifier is started, the Yellow LED will blink to indicate the 1/10s of the version number. Then
the Red LED will blink to indicate the version number. Version 2.1 = 1 flash of the Yellow LED, follwed by 2
flashes of the Red LED.
2.3 Start-up Procedure
After closing the external fused disconnect to put power to the humidifier, press the top (I)
part of the I/O switch on the side of the unit. The unit will then respond to the On/Off
humidistat.
After running the diagnostics, the unit will start operation, or flash an alarm, indicating the
humidifier is disabled or in alarm. The alarm code will flash.
3 Operation
3.1 Manual Drain
Pressing the
▼
button on the side of the humidifier and holding it, will force a manual drain.
3.2 Seasonal Shut Down
During seasonal shut-down or alternatively shut-down for maintenance of the electrical parts and/or the
plumbing, the humidifier should be placed out-of-service.
NOTE: the water cylinder should be emptied before shutting down the humidifier, to prevent corrosion
of the electrodes.
Follow these instructions:
•
Press and hold the manual drain switch until the steam cylinder is empty;
•
Turn off the On/Off (I/O) rocker switch on the side of the humidifier, and disconnect power from the
humidifier;
•
Shut off the water to the humidifier.
In the event of malfunction of the drain valve, the cylinder can be emptied manually by lifting it out of
the drain manifold and pouring the water into the bottom drain pan.