3.4 Cooling
Sufficient air flow (at least 2m/s) and air change must be provided inside the compartment where the system is
placed (made up of fan, compressor and control). The air flow must hit the control from the opposite side to the
electrical connection terminals, to cool the heatsink and compressor. A support has been inserted for housing a 40
mm side fan near the heatsink. The maximum ambient temperature is 45 ° C.
50002730_012_R01
Fig. 3.l
•
ensure the required air flow across the heat sink (at least 2m/s), as specified in the table of technical specifications;
•
avoid shielding the air flow due to the installation of other components.
3.5 Electrical
installation
Caution: