28
Heez +050002745 rel. 1.2 - 16.11.2021
ENG
Table of initial configuration parameters
C
at.
C
ode
D
escription
D
ef
Min
Max
User
Ctl
St
Set point
3.5 °C
r1
r2
U
Ctl
r6
Night time operation: activation delay
0= disabled
4 h
0
999
S
Ctl
r7
Night time operation: duration
10 h
r13
999
S
Ctl
r12
Night time operation: light deactivation delay
0 min
0
999
S
Ctl
r10
Normal operation: light on delay
0 min
0
999
S
Ctl
r13
Recovery time:
0=automatic evaluation of night time set point disabled
4 h
0
r7
S
Ctl
r4
Night time operation: min set point delta
3 °C
-20
r5
S
Ctl
rPc
Night time operation: set point correction
0
-10 (50%) 10 (-50%) S
CFn
HSL
Enable self-learning 0/1 = No/Yes
0
0
1
S
CFn
HSO
Self learning sensitivity
0/1/2 = low/medium/high = 90/60/30 min
1
0
2
S
CFn
HSr
Reset self-learning 0/1 = no/yes
0
0
1
S
dEF
dt
End defrost threshold
1.5 °C
1.5
9.9
S
dEF
ddt
Defrost evaluation time
60 min
0
999
S
dEF
dP
Maximum defrost duration
20 min
0
199
S
rtc
h
Date/time: hour*
-
0
23
S
rtc
m
Date/time: minute*
0
0
59
S
rtc
d
Date/time: day*
-
1
31
S
rtc
M
Date/time: month*
-
1
12
S
rtc
y
Date/time: year*
-
0
99
S
rtc
thS
Time band: start hour*
8 h
0
23
S
rtc
thE
Time band: end hour*
20 h
0
23
S
rtc
tnS
Time band: start minute*
0 min
0
59
S
rtc
tnE
Time band: end minute*
0 min
0
59
S
rtc
tb1…
tb7
Time band: enable day 1…7*
0/1=No/Yes
-
0
1
S
HMI
/r
Buzzer 0/1=No/Yes
1
0
1
S
HMI
/4
Display
0= control temperature
1= intake temperature
2 = result of mitigation algorithm
3 = set point
4 = “.”
0
0
4
S
HMI
/5
Unit of measure 0/1 = °C, bar, cl/°F, psig, FlOz
0
0
1
S
ALM
A10
Door open alarm 1 delay
5 min
0
20
S
Tab. 4.a