Humidisk - user manual
Rel. 1.2 del 18/03/99
10
3.6
Control panel HDE10MP230 for the control of two HDU centrifugal humidifiers
connected in parallel
Fig. 8
The wiring connections to be made on the terminal block of the HDE electrical panel concern connection to the first
humidifier, connection to the second humidifier, to power source, to humidity probe, to alarm output and to remote
On/Off.
Important: when making electrical connections use insulated conductors with 1.5mm² minimum cross-section.
3.6.1 Connecting the HDE10MP230 electrical panel to the first HDU humidifier
Connect the terminal 60 of the electrical panel to the terminal 1 of the humidifier,
the terminal 70 “ to the terminal 3 “
the terminal 80 “ to the terminal 2 “
the terminal 90 “ to the terminal 7 “
the terminal 10 “ to the terminal 9 “
3.6.2 Connecting the HDE10MP230 electrical panel to the second HDU humidifier
Connect the terminal 61 of the electrical panel to the terminal 1 of the humidifier,
the terminal 71 “ to the terminal 3 “
the terminal 81 “ to the terminal 2 “
the terminal 91 “ to the terminal 7 “
the terminal 10 “ to the terminal 9 “
As for the other devices (power source, probe, remote On/Off, see 3.5 above).