18
GB
easy way ARIA +030220841 - rel. 1.0 - 26.10.2007
The time bands can be disabled by setting fi eld 4 as follows
Band 1
Band 2
ON
ON
OFF
OFF
Note
: if HOUR and MINUTES of band 1 (H1M1) = hour and minutes
of band 2 (H2M2), the value of M2 is automatically increased by 1
minute.
Example
: with manual set point 21°C.
Fig. 4.c.e
Time bands from the supervisor
If the control of the time bands is transferred to the Master supervisor
device (pCO, PlantVisor,...), the local time bands can be disabled and the
corresponding symbols
and
controlled independently to inform
the user of the active time band.
par.
description
min
max
def
UOM
type
index
R/W
notes
-
Enable time bands from supervisor
0
Local time bands
1
Control of time band symbols from supervisor (I16)
0
1
0
-
D
12
W
-
-
Time band index from the supervisor, if D12 active
0
no time band symbol displayed
1
time band 1 symbol displayed
2
time band 2 symbol displayed
0
2
0
-
I
16
W
-
-
Sleep mode status
0
instrument not in sleep mode
1
instrument in sleep mode
0
1
0
- D 7
R/W
-
Tab. 4.d