Carel easy way aria Скачать руководство пользователя страница 10

10

GB

easy way ARIA +030220841 - rel. 1.0 - 26.10.2007

The following chapter describes an example of the procedure for setting 
the address, confi guring and connecting the devices for the creation of 
a wireless domain connectable to a Master controller using the CAREL 
protocol (pCO, PlantVisor, PlantWatch,…).

The procedure includes:

setting the address of the access point

1. 

setting the address of the terminals

2. 

setting the address of the sensors

3. 

connecting the modes. In this phase, the terminals and the sensors 

4. 

are associated with the access point.

3.1  Example of the wireless network

1 Access point (EW00AB2020)

• 

1 Repeater (EW00RB2020) (if necessary)

• 

2 Terminals (EW00T*)

• 

2 Sensors (EW00S*)

• 

Fig. 3.a

3.2  Setting the addresses

This is a fundamental phase in setting up the system, and allows each 
device to be identifi ed uniquely.

Important

: the address can only be set at this time. Any changes, 

when the channel has been set (see Automatically search for 

wireless communication channel), will be ignored. The address can only 
be changed after having reinitialised the device (see Resetting the 
devices).

Access point

Power up the access point;

• 

check that LED L1 (yellow) on the left is always on and the others are 

• 

off . If the LEDs are not in this status, reinitialise the access point (see 
Resetting the devices);

Set the desired CAREL network address using the 4 dipswitches (0 = 

• 

OFF; 1 = ON), as shown in the table.

 Fig. 3.b

CAREL address

dip switch

notes

1

2

3

4

0

0

0

0

0

Address not allowed (*)

1

1

0

0

0

2

0

1

0

0

3

1

1

0

0

4

0

0

1

0

5

1

0

1

0

6

0

1

1

0

7

1

1

1

0

8

0

0

0

1

9

1

0

0

1

10

0

1

0

1

11

1

1

0

1

12

0

0

1

1

13

1

0

1

1

14

0

1

1

1

15

1

1

1

1

Tab. 3.a

(*)The address can be set but the device will not respond to the requests 
from the Master.

Automatically search for the wireless communication 
channel

The wireless system requires of use a transmission channel for the 
communication of the wireless messages between the various devices.
The best communication channel for the environment in question is 
automatically selected by the access point, using the following procedure:

power up the access point (the left LED must be on steady);

• 

press the button and check the activation sequence:

• 

for around 10 seconds

3.  CONFIGURATION

Содержание easy way aria

Страница 1: ...sy way aria User manual easy way ARIA is the first completely wireless CAREL solution for the management of ambient comfort in buildings It guarantees energy saving and optimisation of the entire syst...

Страница 2: ......

Страница 3: ...uct should be used or stored in environments that comply with the temperature and humidity limits specified in the manual do not attempt to open the device in any way other than described in the manua...

Страница 4: ......

Страница 5: ...of the wireless network 10 3 2 Setting the addresses 10 3 4 Connecting the devices Binding 12 3 5 Reset devices 13 3 6 Wireless variables 14 4 TERMINAL 15 4 1 Display 15 4 2 Keypad 15 4 3 Functions 2...

Страница 6: ......

Страница 7: ...individual zones energy saving the now mature ZigBee technology used for wireless communication ensures high security of the data exchanged mesh layout between the access point and Repeaters 1 4 Termi...

Страница 8: ...it rate of 250 kbit s Types of nodes ZigBee Coordinator easy way access point Must be available in every network Coordinates the creation of the network ZigBee Router easy way Repeater Participates in...

Страница 9: ...ncy of radio transmission is reduced when there are obstacles metal shelving or other objects that may block the reception of the wireless signals if the product is wall mounted fasten it to a masonry...

Страница 10: ...can only be changed after having reinitialised the device see Resetting the devices Access point Power up the access point check that LED L1 yellow on the left is always on and the others are off If t...

Страница 11: ...ired CAREL network address for the parameter loc09 par description min max def UOM type index R W notes loc 9 Supervisor address of the device 16 199 16 I 4 R W R only from supervisor loc 10 Password...

Страница 12: ...ng opened the domain on the access point Access the parameters menu see paragraph 4 5 Enter the password 22 default for parameter loc 10 Set parameter loc12 to ON the terminal displays bin and subsequ...

Страница 13: ...nd the system is ready for data communication Note each terminal sensor should be visible from at least two devices either access point or repeater In the event of a repeater fault in this way the ter...

Страница 14: ...ry n minutes where n is decided by the user based on the application Battery level Indicates the current charge of the battery on the terminal sensor This mainly depends on the time set between transm...

Страница 15: ...inal off 2 Time Bands Pressed briefly Enter time band setting mode Pressed and held 5 s Enter clock setting mode 3 Fresh Air Pressed briefly Change percentage of Fresh Air UP DOWN buttons to change va...

Страница 16: ...OFF ON 0 D 14 R W password access The parameter is used to enable disable the use of the heater for AUTO and HEAT modes The terminal does not control the status of the heater but rather tells the sup...

Страница 17: ...imes Fig 4 c c Fig 4 c d Key enter time band setting mode by pressing once Band 1 can now be programmed with hour digits flashing Enter the start hours for band 1 using the UP and DOWN buttons 1 Press...

Страница 18: ...er supervisor device pCO PlantVisor the local time bands can be disabled and the corresponding symbols and controlled independently to inform the user of the active time band par description min max d...

Страница 19: ...pervisor I10 I11 When written the value returns to 0 0 1 0 D 13 R W Terminal hours 0 23 Hours I 8 R Terminal minutes 0 59 Min I 9 R Supervisor hours Write enabled using D13 0 23 Hours I 10 W Superviso...

Страница 20: ...isplays the configured functions in sequence Each time the UP DOWN button is pressed increases decreases the function selected where modifiable To exit the selected function By time 5 seconds after th...

Страница 21: ...perature COMFORT displayed if COMFORT function active loc 3 Humidity if humid sensor not fitted 4 Set Humidity Tab 4 h Secondary display loc2 Fig 4 d c loc2 display notes 0 no display Blank 1 Temperat...

Страница 22: ...smission 0 1 5 0 1 0 C A 4 R W Minimum humidity variation to force transmission 1 0 10 0 5 0 rH A 5 R W Temperature from supervisor if D11 1 40 0 80 0 0 0 C A 10 W Humidity from supervisor if D11 1 1...

Страница 23: ...then visible on the terminal The function can be activated using parameter loc20 par description min max def UOM type index R W notes loc 20 Display set point COMFORT 0 set point 1 COMFORT 0 1 0 D 15...

Страница 24: ...def UOM type index R W notes loc 19 Occupancy profile 0 disabled 2 configuration 2 1 configuration 1 3 configuration 3 0 3 0 I 18 R W password access All values other than 0 are equivalent and enable...

Страница 25: ...isor pCO controller PlantVisor PlantWatch to change the ambient set point as follows Set point Current set point loc4 in cooling mode or with cooling request AUTO Set point Current set point loc4 in h...

Страница 26: ...In the algorithm is disabled RC 0 RH 0 The function is disabled if Diff 0 RH The humid request RU is enabled in ou The dehumid request RD is enabled in ou symbol description min max def um type index...

Страница 27: ...the normal display The alarms are also highlighted on the display by the following symbol Fig 4 e a par description min max def UOM type index R W notes Local temperature sensor alarm 0 no temperatur...

Страница 28: ...for 3 s accesses the parameters menu Multifunction Set and confirm changes UP Increase parameter value index DOWN Decrease parameter value index Tab 4 t Access Fig 4 f a To access parameter programmin...

Страница 29: ...It can be changed By setting a parameter on the terminal loc11 Access the parameters menu Enter the password for loc10 Set loc11 to the desired value Fig 4 f d Via supervisor Set the following paramet...

Страница 30: ...device without binding 16 199 16 I 4 R W loc 10 Enter password to access the factory parameters 0 999 22 R W loc 11 Value of the password to access the factory parameters 0 no access password n access...

Страница 31: ...button 1 3 5 6 not active 2 3 14 lock button 2 3 5 7 not active 1 2 3 15 lock button 1 2 3 5 0 15 0 I 27 R W loc 19 Occupancy profile 0 disabled 1 configuration 1 2 configuration 2 3 configuration 3 0...

Страница 32: ...dity variation to force transmission 1 0 10 0 5 0 rH A 5 R W Temperature set point 8 0 32 0 25 0 C A 6 R W Humidity set point 0 0 100 0 50 0 rH A 7 R W Indicative wireless signal level 100 0 30 0 Dbm...

Страница 33: ...100 50 I 7 R W Terminal hours 0 23 hrs I 8 R Terminal minutes 0 59 Min I 9 R Supervisor hours Write enabled using D13 0 23 hrs I 10 W Supervisor minutes Write enabled using D13 0 59 0 Min I 11 W Occup...

Страница 34: ...I 25 R W 7 0 loc 15 Field displayed when pressing multifunction the fifth time 0 no display 4 Humidity value 1 temperature set point 5 display clock 2 Temperature value 6 enable sleep timer 3 Humidit...

Страница 35: ...protection IP20 Classification according to protection against electric shock Can be integrated in class 1 and 2 equipment Environmental pollution Normal PTI of insulating materials 250V Period of st...

Страница 36: ...range 80 RH non condensing Storage conditions 20T70 C humidity range 80 RH non condensing Precision of temperature measurement 1 C 10T40 C 2 C 0T50 C Precision of humidity measurement 5 20 to 80 RH In...

Страница 37: ...als for power supply power supply terminal plug in cables max size 1 5 mm LAN 485 communication terminal plug in cables max size 1 5 mm2 use shielded cable with shield connected to GND Type of cable S...

Страница 38: ...ating conditions 0T50 C 80 RH non condensing Storage conditions 20T70 C 80 RH non condensing Connections screw terminals for power supply power supply terminal plug in cables max size 1 5 mm Type of c...

Страница 39: ...n the access point and the terminal sensor this may occur when The distance between the access point and the terminal sensor is greater than 50 m with visibility between the devices Fig 6 i a Fig 6 i...

Страница 40: ...tivity 90 dB maximum current 35 mA current in standby 1 A domain levels 7 maximum number of wireless network devices 199 of which 15 Access Point 184 terminals sensors maximum 5 repeaters in cascade c...

Страница 41: ...Notes...

Страница 42: ...Note...

Страница 43: ......

Страница 44: ...Brugine Padova Italy Tel 39 049 9716611 Fax 39 049 9716600 e mail carel carel com www carel com Agenzia Agency easy way ARIA 030220841 rel 1 0 26 10 2007 CAREL reserves the right to modify the featur...

Отзывы: