ENGLISH

DPDQ 402000

DPDQ 402000

  

including mounting flange

APPLICATION:
Patented quality product  (patent no. DE 10 2014 010 719.1)

The maintenance-free, microprocessor-controlled duct CO

2

 sensor is designed for duct installation 

and is used to detect the CO

2

 content of the air. The measurement signals are converted to standard 

signals of 0 -10 V or 4...20 mA.   

The CO

content of the air is measured using an optical NDIR sensor (non-dispersive infra-red technology). 

The detection range of the CO

2

 sensor is calibrated for standard applications such as monitoring residen-

tial rooms and conference rooms. Room ventilation on an as-needed basis, improved well-being and 
 customer benefit, increased comfort as well as reduced operating costs through energy conservation are 
just some of the benefits of employing CO

2

 sensors.  

A measuring system based on NDIR (non-dispersive infra-red technology) for CO

2

 measurement consists 

of a light source and a receptor. A certain range of wavelengths of light radiated by the source is damped 
and absorbed by CO

2

 molecules in the measured section. This damping is detected by the receptor.  

TECHNICAL DATA:

Power supply: 

24 V AC ⁄ DC (± 10 %)

Power  consumption:  

< 1.5 W  ⁄  24 V DC  typical;  < 2.9 VA  ⁄  24 V AC typical;  
Peak current 200 mA

Sensor, CO

2

:  

optical NDIR sensor (non-dispersive infra-red technology) 

with automatic and manual calibration

Measuring range, CO

2

:  

Multi-range switching

 (selectable via DIP switches) 

0...2000  ppm;  0...5000  ppm

Output, CO

2

:  

0 -10 V   

or  

4...20 mA

  (selectable via DIP switches)   

1 changeover contact (24 V / 1 A) 
switchpoint adjustable

Measuring accuracy, CO

2

:  

± 30 ppm  ± 3 %  of  measured  value

Temperature dependence, CO

2

:  ± 5 ppm   ⁄  °C  or   

± 0.5 %  of  measured  value   ⁄  °C     
(whichever is higher)

Pressure  dependence:  

± 0.13 %   ⁄  mm  Hg

Long-term stability:  

< 2 % in 15 years

Gas exchange:  

by diffusion

Warm up time:  

approx. 1 hour

Ambient  temperature:  

–10...+60 °C

Response  time:  

approx.  1 minute

Electrical connection:  

0.14 - 1.5 mm

2

, via screw terminals

Enclosure:  

plastic,  UV-stabilised, material polyamide, 30 % glass-globe reinforced,   
with quick-locking screws (slotted ⁄ Phillips head combination),  
colour traffic white (similar to RAL 9016)

Enclosure  dimensions:  

72  x  64  x  37.8 mm

Cable gland:  

M 16 x 1.5; including strain relief, exchangeable,  
max. inner diameter 10.4 mm

Protective tube: 

PLEUROFORM

TM

, material polyamide (PA6), with torsion protection,  

Ø  20 mm,  NL = 202.5 mm,  v

max

 = 30  m/s (air) 

Process connection: 

via flange made of plastic  (included in scope of delivery)

Protection class: 

III  (according to EN 60 730)

Protection type: 

IP 65  (according to EN 60 529)  enclosure only ! 

Standards: 

CE conformity,  
electromagnetic compatibility according to EN 61 326,  
EMC Directive 2014 ⁄ 30 ⁄ EU  

DIP switches 

DPDQ 402000

CO

2

 content

DIP 1

0...2000 ppm  (default)

OFF

0...5000 ppm

O N

CO

2

 automatic zero point

DIP 3

deactivated

OFF

activated  (default)

O N

Output

DIP 4

Voltage 0 -10 V  (default)

OFF

Current  4...20 mA

O N

Note:  

DIP 2 

is not assigned!  

Содержание DPDQ402000

Страница 1: ...B VIII 17 050001301 REL 3 0 08 08 2017 Operating instructions mounting installation DPWQ 402000 Room CO2 sensor with self calibrating with multi range switching active and switching output DPDQ 402000...

Страница 2: ...value Temperature dependence CO2 5 ppm C or 0 5 of measured value C whichever is higher Pressure dependence 0 13 mm Hg Long term stability 2 in 15 years Gas exchange by diffusion Relay output with po...

Страница 3: ...Measuring Range CO2 Output CO2 Features DPWQ 402000 0 2000 0 5000 ppm 0 10 V 4 20 mA Changeover contact Note This unit must not be used as safety relevant device 1 2 3 1 2 3 4 5 ON DIP zero set offse...

Страница 4: ...and manual calibration Measuring range CO2 Multi range switching selectable via DIP switches 0 2000 ppm 0 5000 ppm Output CO2 0 10V or 4 20mA selectable via DIP switches 1 changeover contact 24 V 1 A...

Страница 5: ...ntact Note This unit must not be used as safety relevant device Schematic diagram DPDQ 402000 1 2 3 4 ON DIP SET Zero OFFSET 13 11 12 1 2 3 Breaker Normally open contact Output CO in ppm UB GND UB 24V...

Страница 6: ...not correlate to the factory preset definition range and calibration Please note that factory calibration is thereby lost and compliance with technical data can no longer be guaranteed ATTENTION The m...

Страница 7: ...logen spotlights must absolutely be avoided Operating this device close to other devices that do not comply with EMC directives may influence functionality This device must not be used for monitoring...

Страница 8: ...ler of the final equipment accepts all liability and risk relating to the configuration of the product in order to reach the expected results in relation to the specific installation and or equipment...

Отзывы: