background image

12

 •  The installation of both anti-derailment buffers is 

absolutely obligatory

 before starting programming.

•   Make sure the safety devices are at rest and the ECU is receiving mains power otherwise you will not be able to enter programming.
•  Choose the type of geared motor you are using from the "

display menu

" (page 13).

PROGRAMMING PROCEDURE (Setting the programmer and the current sensor)

Dip-switch settings DS1

CAUTION:

 If you change the dip settings you must memorise them; press the 

"PROG" 

button, "dIP" will appear on the display indicating that the settings have 

been memorised.

Motor selection (DIP1)

"ON"   =  Single motor operation

"OFF"  =  Double motor operation

Opening direction gate delay (DIP 2)

"ON"   =  Opening direction gate delay enabled
"OFF"  =  Opening direction gate delay disabled

If you enable gate delay the following will occur: during the opening movement gate 

leaf 1 moves first and then gate leaf 2. In the closing direction gate leaf 

2

 

moves 

first then gate leaf 1. If gate delay is disabled both gate leaves move simultaneously.

Sequential command TD/CH1 (DIP3)

"ON"   =  Sequential command "open-close"

Travel direction inversion only during closing.

"OFF"  =  Sequential command "open-block-close-block"

Automatic reclosing (DIP4)

"ON"   =  Automatic reclosing enabled
"OFF"  =  Automatic reclosing disabled

Pre-flashing (DIP 5)

"ON"   =  Pre-flashing activated
"OFF"  =  Pre-flashing excluded

Warning light output (DIP 6)

"ON"   =  Warning light output intermittent 
"OFF"  =  Warning light output fixed

Indicator light (DIP 7)

"ON"   =  Indicator light intermittent

*

 

"OFF"  =  Indicator light fixed

The indicator light flashes slowly during opening, rapidly during closing; remains 

lit when the gate is blocked but not completely closed

 

and is off when the gate 

is completely closed.

FTCI mode (DIP 8)

"ON"   = 

FTCI

 also active when the gate is blocked

If the photocells are in alarm and the gate is blocked, no movement commands 

will be accepted (even opening commands).

"OFF"  = 

FTCI

 active only during closing

In both cases activating the 

FTCI

 safety device during the closing stage will force 

travel direction inversion.

FTCI test (DIP 9)

"ON"   = 

FTCI

 test enabled

"OFF"  = 

FTCI

 test disabled

If you enable the security test you will have to connect both the transmitter and 

the receiver to the controlled load output (

CTRL

 

24 Vdc

). When the test is enabled 

one second will pass between receiving a command and carrying it out. 

FTCS test (DIP 10)

"ON"   = 

FTCS

 test enabled

"OFF"  = 

FTCS

 test disabled

If you enable the security test you will have to connect both the transmitter and 

the receiver to the controlled load output (

CTRL

 

24 Vdc

). When the test is enabled 

one second will pass between receiving a command and carrying it out. 

Electric lock (DIP 11)

"ON"   =  Electric lock enabled

"OFF"  =  Electric lock disabled

If the electric lock is enabled the ELS output (binding post 6) will be activated 

before gate leaf 1 moves and will remain active until gate leaf one has moved a 

few centimetres.

Travel limit motor 1 (DIP 12)

“ON”    =  Travel limit motor 1 enabled
“OFF”   =  Travel limit motor 1 disabled

Travel limit motor 2 (DIP 13)

“ON”    =  Travel limit motor 2 enabled
“OFF”   =  Travel limit motor 2 disabled

Dip 14

  =  Not used

WHEN THE GATES REACH THE COMPLETELY OPEN POSITION THEY INVERT THE TRAVEL 

DIRECTION AND AFTER MOVING FOR A FEW CENTIMETRES THEY WILL OPEN AGAIN TO 

CONFIRM THE COMPLETELY OPEN POSITION. AT THIS POINT THE LEAVES MOVE ONE AT A 

TIME IN THE CLOSING DIRECTION (FIRST GATE LEAF 2). WHEN ONE OF THE GATE LEAVES 

REACHES THE COMPLETELY CLOSED POSITION IT INVERTS THE TRAVEL DIRECTION AND 

AFTER MOVING FOR A FEW CENTIMETRES IT WILL CLOSE AGAIN TO CONFIRM THE 

COMPLETELY CLOSED POSITION.  

AFTER HAVING CARRIED OUT THIS MANOEUVRE THE LOGIC CONTROL WILL OPEN THEN 

CLOSE THE GATE LEAVES COMPLETELY IN ORDER TO CALIBRATE THE CURRENT SENSOR. 

WHEN THE GATE REACHES THE 

COMPLETELY CLOSED POSITION THE 

PROGRAMMER SAVES THE PARAMETERS 

AND QUITS THE PROGRAMMING MODE

THE OPERATION HAS NOT 

SUCCEEDED. YOU WILL HAVE 

TO REPEAT THE 

PROGRAMMING PROCEDURE.

PRESS THE 

PROG

 BUTTON FOR MORE 

THAN 4 SECONDS: THE "

PAUSE

" SYMBOL 

WILL APPEAR INDICATING THAT YOU ARE 

IN THE PAUSE PROGRAMMING MODE

1...4... sec.

PRESS PROG

THE PAUSE TIME COUNT 

ENDS AND THE DOOR OPENS 

SLOWLY IN ORDER TO FIND 

THE COMPLETELY OPEN 

POSITION. 

THE PAUSE TIME COUNT 

WILL START (

MIN. 2 

SECONDS: MAX 120 

SECONDS

) INDICATED BY 

THE "

PAUSE

" SYMBOL 

FLASHING ON THE DISPLAY 

PRESS PROG

ATTENTION!

 IF THE GATE MOVES 

IN THE CLOSING DIRECTION THE 

MOTOR CONNECTION IS 

INCORRECT.  PRESS “

PROG

” 

AGAIN TO CANCEL THE 

PROGRAMMING PROCEDURE, 

INVERT THE MOTOR 

CONNECTION (RED AND BLACK 

CABLE) AND REPEAT THE 

PROGRAMMING PROCEDURE.

CURRENT SENSOR

The programmer checks the electrical input to the motor, detecting any eventual 

increase in effort above the normal operating limits and intervenes as an additional 

safety device. If the sensor intervenes during the opening direction the gate inverts 

the travel direction immediately and proceeds to the fully open position. If the 

sensor intervenes during the closing direction the gate automatically inverts the 

travel direction of a few centimetres and then stops to free the obstacle.

Repositioning

Attention!

 During the repositioning manoeuvre the current sensor value “

SnS

could be different leading to a momentary increase in the door impact force. At 

the end of the manoeuvre, however, it will reset automatically to the chosen value.

If a prooblem occurs after a programmer reset 

 , when one of the motors has 

been released 

 

 or there is a problem with one of the motors 

 

 the 

warning lights and indicator light will flash simultaneously for 

2 seconds

 and will 

then switch off for 

10 seconds

If in this stage you send a (

TA, TC, TAL 

or

 TD

) command to the programmer. 

The programmer will move the gates slowly  to the completely closed position (2 

times as in the programming procedure) in order to recover the correct position. 

At this point the programmer will function normally. If a “

TA

" command is given 

the positioning recovery is carried out in the opening direction.

No commands will be accepted during repositioning but the security devices will 

cut in and block all movement if they go into alarm.

To interrupt the repositioning manoeuvre press the “

PROG

" or “

TB

" button.

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

Содержание 24S-24L

Страница 1: ...enWerkst ttenderHerstellerfirmaaufdieperfekte bereinstimmung bereinstimmung seiner Eigenschaften mit den von den geltenden Normen vorgeschriebenen Merkmalengetestetund berpr ft Esteproductohasidoproba...

Страница 2: ...1 LEGEND 1 Geared motor SX left 2 Geared motor DX right 3 Internal photocells 4 External photocells 5 Warning lights 6 Mechanical selector switch 7 Electric locking device 8 External antenna RG58 coa...

Страница 3: ...FAHREN ESQUEMA DE MONTAJE 200 BLA24S 200 BLA24L SCALA 1 2 Prodotti TELCOMA BLA24 DI0290 Description Product Code Drawing number All rights reserved Unauthorised copying or use of the information conta...

Страница 4: ...reserved Unauthorised copying or use of the information contained in this document is punishable by law 476 350 137 893 476 500 1043 137 3 SCHEMA DI MONTAGGIO ASSEMBLY DRAWING SCH MA DE MONTAGE MONTAG...

Страница 5: ...Unauthorised copying or use of the information contained in this document is punishable by law 105 55 94 27 8 5 10 5 4 SCHEMA DI MONTAGGIO ASSEMBLY DRAWING SCH MA DE MONTAGE MONTAGEVERFAHREN ESQUEMA...

Страница 6: ...240 200 270 240 1 200 BLA24L E 970 mm C A B alfa max 90 B alfa max 120 80 150 130 B 170 90 160 130 B 180 100 170 130 B 170 170 B 210 110 180 130 B 180 180 B 200 120 190 170 B 210 210 B 250 130 200 18...

Страница 7: ...ned in this document is punishable by law SEL 24V 12V 0 C 1 6 5 4 3 2 NA NC NC C NA FTC RX 1 3 2 CLOSING COMMON OPENING 1 3 2 24V 12V 0 FTC TX 1 2 1 2 ELS LP BRIDGE CMN CMN FTCI N C TD N O CMN TA N O...

Страница 8: ...e recycling of materials Illicitly disposing of this product by the owner is punishable by law and will be dealt with according to the laws and standards of the individual member nation During the ope...

Страница 9: ...or one or two motors Before connecting the appliance make sure that the voltage rated on the data plate conforms to that of the mains supply The appliance works off a 24V direct current power supply s...

Страница 10: ...ebenen getestet und gepr ft Este producto ha sido probado y ensayado en los laboratorios del fabricante que ha comprobadolaperfectacorrespondenciadesuscaracter sticasconlascontempladasporlanormativavi...

Страница 11: ...1 22 23 24 LC CH2 5 6 1 2 M1 CMN ELS 12V LS TAL N O FTCS N C P1 J1 B1 CS 1435 DC 0535 35 34 J4 R1 L9 L8 L6 L5 L10 L7 L4 P3 P2 L3 1 2 3 4 5 6 7 8 9 10 11 12 13 14 ON DS1 1 2 3 J5 Pos 1 Pos 2 1 2 3 CSP...

Страница 12: ...e product conforms in every aspect to the safety standards in force Any non authorised modifications are to be considered improper dangerous and the complete responsibility of the installer This appli...

Страница 13: ...Dip 10 OFF IfyouwanttoactivatetheFTCI FTCStestboththetransmissionandreceiverparts of the security devices must be connected to the binding post marked CTRL 24 Vdc If the test is active there will be...

Страница 14: ...motor 2 enabled OFF Travel limit motor 2 disabled Dip 14 Not used WHEN THE GATES REACH THE COMPLETELY OPEN POSITION THEY INVERT THE TRAVEL DIRECTION AND AFTER MOVING FOR A FEW CENTIMETRES THEY WILL OP...

Страница 15: ...ng changes Deceleration settings 1 Minimum 3 Maximum 2 Medium PRESS PROG Each time the button is pressed the number increases from 1 to 3 10 sec 10 s after the last modification you will automatically...

Страница 16: ...he transmitter channel buttons memorised will activate their signal buzzer B1 fig 1 3 Press one of the channel buttons on the same transmitter The receivers which do not contain that channel code will...

Страница 17: ...oor The self sufficiency of the system when it is running on battery power is dependent on the ambient conditions and on the load connected at binding posts 13 14 power is always routed there during b...

Страница 18: ...ng This happens when an N C contact is activated FTCI FTCS CSP during time programming or repositioning Once the passive state of the security devices has been reset the gate door will start moving ag...

Отзывы: