Package Air Conditioners
Nut 1
Nut 2
Setting lever
Tensiometer
Note: Above diagrams may be different from actual model.
4.Electrical Installation
4.1 Electrical Date and Wire Sizing
Unit Model
Designation
Power Supply (V, Ph,
Hz)
Capability of
Air Switch(A)
Min. Sectional Area
of Earth Wire(AWG)
Min. Sectional
Area of Power
Cord(AWG)
CGK-C03NC1AD
220V,1Ph,60Hz
40
8
8
CGK-C03TC1AD
220V,1Ph,60Hz
40
8
8
CGK-C03TC1AK
220V,1Ph,50Hz
40
8
8
CGK-C04NC1AD
220V,1Ph,60Hz
60
4
4
CGK-C04TC1AD
220V,1Ph,60Hz
60
4
4
CGK-C04TC1AM
380-415V,3Ph,50Hz
25
12
12
CGK-C05NC1AD
220V,1Ph,60Hz
60
4
4
CGK-C05NC1AF
220V,3Ph,60Hz
40
8
8
CGK-C05TC1AF
220V,3Ph,60Hz
40
8
8
CGK-C05TC1AM
380-415V,3Ph,50Hz
25
12
12
CGK-H05TC1AM
380-415V,3Ph,50Hz
25
12
12
CGK-C08TC1AF
220V,3Ph,60Hz
60
4
4
CGK-C08TC1AM
380-415V,3Ph,50Hz
40
8
8
CGK-H08TC1AM
380-415V,3Ph,50Hz
40
8
8
CGK-C10TC1AF
220V,3Ph,60Hz
60
4
4
CGK-C10TC1AM
380-415V,3Ph,50Hz
120
2
2
CGK-H10TC1AM
380-415V,3Ph,50Hz
4
0
8
8
CGK-C13TC1AF
220V,3Ph,60Hz
120
2
2
CGK-C15TC1AF
220V,3Ph,60Hz
120
2
2
CGK-C15TC1AM
380-415V,3Ph,50Hz
100
2
2
CGK-H15TC1AM
380-415V,3Ph,50Hz
100
2
2
CGK-C20TC1AF
220V,3Ph,60Hz
160
1/0
1/0
CGK-C20TC1AM
380-415V,3Ph,50Hz
125
2
2
CGK-C25TC1AF
220V,3Ph,60Hz
200
3/0
3/0
CGK-C25TC1AM
380-415V,3Ph,50Hz
125
2
2
CGK-C30TC1AM
380V,3Ph,50Hz
125
1
1