Package Air Conditioners
Three Phase (380-415V 3-50 POWER SUPPLY)
Model:
C
GK-C10TC1AM,
C
GK-C15TC1AM,
C
GK-C20TC1AM,
C
GK-C25TC1AM
(380-415V 3N~ 50Hz)
Electric Box
GROUND
THERMOSTAT
POWER
Three Phase (380V 3-50 POWER SUPPLY)
Model:
C
GK-C30TC1AM
(380V 3N~ 50Hz)
Electric Box
GROUND
THERMOSTAT
POWER
Apply to cooling with electric heat units:
C
GK-C10TC1AM,
C
GK-C13TC1AF,
C
GK-C15TC1AM,
CGK-
C20TC1AM,
C
GK-C25TC1AF,
C
GK-C25TC1AM,
C
GK-C30TC1AM
TERMINAL
FUNCTION
R
power supply for the wired
controller
C
power supply for the wired
controller
Y
start the compressor and
outdoor (condensing side) fan
motor
G
start the indoor (evaporating
side) fan motor
W1
startup electrical heater
W2
startup electrical heater
Caution:
When it is cooling operation, “Y”, “G” must be started; when it is heating operation, “Y” must be
shut down, and either of “W1” or “W2” must be started, or both. When electrical heater is startup, both
compressors and outdoor fan motors will be shut down automatically. If cooling operation is required, please
make sure that electrical heater has been shut down.
R
C
Y
G
W1
W2
RUNNING
MODE
COOLING
HEATING
(10KW/15KW
heater)
HEATING
(10KW/15KW
heater)
HEATING
(20KW/30KW
heater)