Removing the PCB

Follow the steps below to remove the Cardax FT Controller PCB from the Cardax FT
Cabinet:

1.

Ensure that the power to the Cardax FT Controller 3000 is switched off and
disconnected.

2.

Following full antistatic precautions, disconnect all cables from the Cardax FT
Controller PCB.  Remember to label each cable as you remove it.

3.

Remove the 9 x M3 securing screws that hold the PCB onto the Cardax FT Cabinet
fixing standoffs.

4.

Carefully lift the PCB clear of the Cabinet.

Replacing the PCB

1.

To  replace the Cardax FT Controller PCB, reverse the above procedure.

Note:  You must then initialise the Cardax FT Controller 3000 as detailed

  earlier in this Installation Note.

Connector wiring

Ethernet

10BaseT

The 10BaseT Ethernet connects to socket P2 via an RJ45 connector.

1

+TXD

2

-TXD

3

+RXD

4-5

Not used

6

-RXD

7-8

Not used

9-10

Not used (metal casing)

1

   8

Содержание FT Controller 3000

Страница 1: ...andI Ofunctionalityintoasingleproduct CardaxFTLocalBUS connectionsarenotsupported Reader Interface InterfacestoreadersandassociatedI Oaresetupasfourdistinctgroups numbered1to4 EachgroupisthesameandprovidesconnectiontoeitheroneWiegandortwoCardaxIV readers andfourbalanced 4 state inputsandtwogeneralpurposerelayoutputscapableof switching24voltsDC AC 5Aresistiveloads Eachgroupisalsoprovidedwitha12VDC ...

Страница 2: ...eapproximately0 5VDClowerthanthevoltagesupplied totheCardaxFTController3000 Thefusesareresettable i e underfaultconditions fuses gohighresistance Whenthefaultsubsidesorpowerisremoved thenthefuseswillcooland resetthemselves Thecurrentloadontheseconnectionpoints PA1toPA4 isinadditiontothe1 0Arequired bytheCardaxFTController3000 Whenusingtheseconnectionpoints ensurethePower SupplytotheCardaxFTControl...

Страница 3: ...nectedtoplugP3 Balanced Inputs Cablingshouldbeaminimumsizeof0 2mm2 24AWG forallinputs Toensurecorrecttamperdetection shortoropencircuit thebalancedinputsrequire4k7 ohmresistorstobeconnectedascloseaspossibleto thedevicebeingmonitored Whenthemonitoreddeviceincorporatesanormally closedtamperswitch itcanbewiredin serieswithresistorR1 Alarm sensor Input plug 4k7 GND 5 V R2 4k7 R1 4k7 RefertoChapter2oft...

Страница 4: ...ableclampsfittedintothebaseoftheCabinet Refertothenextsection Componentlayout forthelocationoftheplugs PA1 to PA4 Powerout PB1 to PB4 Readerports PC1 to PC4 Balancedinputs PD1 to PD4 Balancedinputs P1 Powerin P2 10BaseTEthernetport P3 Dial upRS232port P4 RS485 PE1 to PE4 Relayoutputs PF1 to PF4 Relayoutputs Remember Thebalancedinputsrequirethe4k7ohmresistorstobeconnectedasclose aspossibletothedevi...

Страница 5: ...UT VOUT VOUT VOUT PA4 PA3 PA2 PA1 2 1 2 1 2 1 2 1 PA4 POWER OUT PA3 POWER OUT PA2 POWER OUT PA1 POWER OUT COMB OUT2 COMA OUT1 DATA1 DATA1 DATA1 DATA1 DATA0 DATA0 DATA0 DATA0 PB4 PB3 PB2 PB1 2 3 1 4 2 3 1 4 2 3 1 4 2 3 1 4 COMA OUT1 COMA OUT1 COMA OUT1 COMB OUT2 COMB OUT2 COMB OUT2 2 3 1 IN2 IN2 IN2 IN2 GND IN1 IN1 IN1 IN1 PC4 PC3 PC2 PC1 2 3 1 2 3 1 2 3 1 GND GND GND IN4 IN4 IN4 IN4 GND IN1 IN1 IN...

Страница 6: ...normalrunningsequence Note Thesectiontitled RunLED laterinthischapter detailsthedifferentmeanings ofthevariousflashsequences 4 Set switch 2 to OFF open Dial up Serial setup details RefertotheDial up Null ModemInitialisationsectionofChapter23intheCardaxFT CommandCentreUserGuide fortheprocedure Optical tamper detectors ThefrontopticaltamperdetectorwillsensewhentheCabinetdoorisopened Therearopticalta...

Страница 7: ...startup themaincodedoesnotrun Instead thelocal configprogramattemptstoestablishconnectionviaserial COM port OFF On startup the main application e g B201b4 exe is run DS6 OFF Unused DS7 OFF Unused DS8 OFF Unused Dip Switch Settings ThefollowingtableshowstheDipSwitchSettings TheSettingsinboldspecifythedefault startupconfiguration Ethernet connection LEDs Component Function LEDwilllightwhen D9 LANAct...

Страница 8: ...d it has connected to the network 4flashes 4flashes pause Noprivatekeyorcertificateloaded eachflashis50mson 400ms seenotebelowforobtainingkeys offandthepauseis1 2s andcertificates 5flashes 5flashes pause Invalidprivatekeyorcertificateloaded eachflashis50mson 400ms orkeyandcertificatedonotmatchthe offandthepauseis1 2s CardaxFTControllerserialnumber 6flashes 6flashes pause The Cardax FT Controller h...

Страница 9: ...mbertolabeleachcableasyouremoveit 3 Removethe9xM3securingscrewsthatholdthePCBontotheCardaxFTCabinet fixingstandoffs 4 CarefullyliftthePCBclearoftheCabinet Replacing the PCB 1 To replacetheCardaxFTControllerPCB reversetheaboveprocedure Note YoumusttheninitialisetheCardaxFTController3000asdetailed earlierinthisInstallationNote Connector wiring Ethernet 10BaseT The10BaseTEthernetconnectstosocketP2via...

Страница 10: ...ththelimitsforaClassBdigital device pursuanttopart15oftheFCCRules Theselimitsaredesignedtoprovide reasonableprotectionagainstharmfulinterferenceinaresidentialinstallation Thisequipment generates uses andcanradiateradiofrequencyenergyand ifnotinstalledandusedin accordancewiththeinstructions maycauseharmfulinterferencetoradiocommunications However thereisnoguaranteethatinterferencewillnotoccurinapar...

Отзывы: