Installation

1.

The  “Cardax FT Cabinet” Installation Note (part number 3C4513) details the
procedures involved to mount the Cardax FT Cabinet:

-

positioning the Cardax FT Cabinet door

-

removing the appropriate cutouts

-

securing the Cardax FT Cabinet to the building.

Note:The Cardax FT Cabinet should be installed in a secure, internal situation. The

security of the installation ultimately depends on the way you install the Cardax FT
Cabinet.

2.

Using the 9 x M3 screws, fit the Controller PCB to the rear face of the Cardax FT
Cabinet, ensuring that the rear tamper sensor aligns with the light pipe.  Also ensure that
the front LED lines up.

3.

Install all the system and power cables. The cables should stow neatly and be held in
place by the cable clamps fitted into the base of the Cabinet.

Refer to the next section “Component layout” for the location of the plugs.

PA1 to PA4

=

Power out

PB1 to PB4

=

Reader ports

PC1 to PC4

=

Balanced inputs

PD1 to PD4

=

Balanced inputs

P1

=

Power in

P2

=

10BaseT Ethernet port

P3

=

Dial-up RS232 port

P4

=

RS485

PE1 to PE4

=

Relay outputs

PF1 to PF4

=

Relay outputs

Remember: The balanced inputs require the 4k7 ohm resistors to be connected as close

as possible to the device being monitored.

4.

Install the component identification decal inside the Cardax FT Cabinet door.  This
decal enables you to enter wiring and connection details and identifies the location and
designation of cable connections, fuses, LEDs, etc.

5.

Initialise the Cardax FT Controller 3000.
The following initialisation procedures are detailed in the later section titled
“Initialisation”:

- Setup details
- Optical tamper detectors

6.

Fix the Cardax FT Product Label to the outside of the Cardax FT Cabinet door and
enter the relevant details.

Содержание FT Controller 3000

Страница 1: ...andI Ofunctionalityintoasingleproduct CardaxFTLocalBUS connectionsarenotsupported Reader Interface InterfacestoreadersandassociatedI Oaresetupasfourdistinctgroups numbered1to4 EachgroupisthesameandprovidesconnectiontoeitheroneWiegandortwoCardaxIV readers andfourbalanced 4 state inputsandtwogeneralpurposerelayoutputscapableof switching24voltsDC AC 5Aresistiveloads Eachgroupisalsoprovidedwitha12VDC ...

Страница 2: ...eapproximately0 5VDClowerthanthevoltagesupplied totheCardaxFTController3000 Thefusesareresettable i e underfaultconditions fuses gohighresistance Whenthefaultsubsidesorpowerisremoved thenthefuseswillcooland resetthemselves Thecurrentloadontheseconnectionpoints PA1toPA4 isinadditiontothe1 0Arequired bytheCardaxFTController3000 Whenusingtheseconnectionpoints ensurethePower SupplytotheCardaxFTControl...

Страница 3: ...nectedtoplugP3 Balanced Inputs Cablingshouldbeaminimumsizeof0 2mm2 24AWG forallinputs Toensurecorrecttamperdetection shortoropencircuit thebalancedinputsrequire4k7 ohmresistorstobeconnectedascloseaspossibleto thedevicebeingmonitored Whenthemonitoreddeviceincorporatesanormally closedtamperswitch itcanbewiredin serieswithresistorR1 Alarm sensor Input plug 4k7 GND 5 V R2 4k7 R1 4k7 RefertoChapter2oft...

Страница 4: ...ableclampsfittedintothebaseoftheCabinet Refertothenextsection Componentlayout forthelocationoftheplugs PA1 to PA4 Powerout PB1 to PB4 Readerports PC1 to PC4 Balancedinputs PD1 to PD4 Balancedinputs P1 Powerin P2 10BaseTEthernetport P3 Dial upRS232port P4 RS485 PE1 to PE4 Relayoutputs PF1 to PF4 Relayoutputs Remember Thebalancedinputsrequirethe4k7ohmresistorstobeconnectedasclose aspossibletothedevi...

Страница 5: ...UT VOUT VOUT VOUT PA4 PA3 PA2 PA1 2 1 2 1 2 1 2 1 PA4 POWER OUT PA3 POWER OUT PA2 POWER OUT PA1 POWER OUT COMB OUT2 COMA OUT1 DATA1 DATA1 DATA1 DATA1 DATA0 DATA0 DATA0 DATA0 PB4 PB3 PB2 PB1 2 3 1 4 2 3 1 4 2 3 1 4 2 3 1 4 COMA OUT1 COMA OUT1 COMA OUT1 COMB OUT2 COMB OUT2 COMB OUT2 2 3 1 IN2 IN2 IN2 IN2 GND IN1 IN1 IN1 IN1 PC4 PC3 PC2 PC1 2 3 1 2 3 1 2 3 1 GND GND GND IN4 IN4 IN4 IN4 GND IN1 IN1 IN...

Страница 6: ...normalrunningsequence Note Thesectiontitled RunLED laterinthischapter detailsthedifferentmeanings ofthevariousflashsequences 4 Set switch 2 to OFF open Dial up Serial setup details RefertotheDial up Null ModemInitialisationsectionofChapter23intheCardaxFT CommandCentreUserGuide fortheprocedure Optical tamper detectors ThefrontopticaltamperdetectorwillsensewhentheCabinetdoorisopened Therearopticalta...

Страница 7: ...startup themaincodedoesnotrun Instead thelocal configprogramattemptstoestablishconnectionviaserial COM port OFF On startup the main application e g B201b4 exe is run DS6 OFF Unused DS7 OFF Unused DS8 OFF Unused Dip Switch Settings ThefollowingtableshowstheDipSwitchSettings TheSettingsinboldspecifythedefault startupconfiguration Ethernet connection LEDs Component Function LEDwilllightwhen D9 LANAct...

Страница 8: ...d it has connected to the network 4flashes 4flashes pause Noprivatekeyorcertificateloaded eachflashis50mson 400ms seenotebelowforobtainingkeys offandthepauseis1 2s andcertificates 5flashes 5flashes pause Invalidprivatekeyorcertificateloaded eachflashis50mson 400ms orkeyandcertificatedonotmatchthe offandthepauseis1 2s CardaxFTControllerserialnumber 6flashes 6flashes pause The Cardax FT Controller h...

Страница 9: ...mbertolabeleachcableasyouremoveit 3 Removethe9xM3securingscrewsthatholdthePCBontotheCardaxFTCabinet fixingstandoffs 4 CarefullyliftthePCBclearoftheCabinet Replacing the PCB 1 To replacetheCardaxFTControllerPCB reversetheaboveprocedure Note YoumusttheninitialisetheCardaxFTController3000asdetailed earlierinthisInstallationNote Connector wiring Ethernet 10BaseT The10BaseTEthernetconnectstosocketP2via...

Страница 10: ...ththelimitsforaClassBdigital device pursuanttopart15oftheFCCRules Theselimitsaredesignedtoprovide reasonableprotectionagainstharmfulinterferenceinaresidentialinstallation Thisequipment generates uses andcanradiateradiofrequencyenergyand ifnotinstalledandusedin accordancewiththeinstructions maycauseharmfulinterferencetoradiocommunications However thereisnoguaranteethatinterferencewillnotoccurinapar...

Отзывы: