Part number 3E1089 R3

March 2003

Procedure

1.

Check the power and Ethernet cabling to the Cardax FT Controller 3000 are correctly
installed.

2.

Locate DIP switch 2 (SW2) on the Cardax FT Controller PCB.
Set switch 2 to ON (closed).

3.

Switch on power to the Cardax FT Controller 3000.  The red LED (D1) flashes in the
following sequence:
(The sequence completes fairly quickly but it is important you ensure the LED finishes
indicating the “normal running” sequence.)

-

The red LED flashes fairly fast during startup.

-

The red LED flashes three times per second. The Cardax FT Controller 3000
is waiting for its IP address.

-

When the Cardax FT Controller 3000 has received its IP number, the red LED
flashes twice per second.  This indicates the Cardax FT Controller 3000 is
waiting for database information to be downloaded from the Server.

-

When initialisation is complete, the LED flashes approximately once per second
indicating a normal running sequence.

Note: The section titled “Run LED” (later in this chapter) details the different meanings

of the various flash sequences.

4.

Set switch 2 to OFF (open).

Dial-up/Serial setup details

Refer to the Dial-up/Null-Modem Initialisation section of Chapter 23 in the Cardax FT
Command Centre User Guide, for the procedure.

Optical tamper detectors

The front optical tamper detector will sense when the Cabinet door is opened.
The rear optical tamper detector will sense if the Cabinet is removed from its mounting
position.

When the Cardax FT Controller 3000 is re-powered after servicing and is operating correctly
it will initialise the optical tamper detectors.

The following procedure will ensure that the optical tamper sensors are initialised correctly on
power-up.

1.

Switch on the 13.6 V DC ± 15%  supply to the Cardax FT Controller PCB.

2.

Close and lock the Cardax FT Controller cabinet door within three seconds, (i.e. before
the Controller goes into a three flash or normal running state).

Note: The Cabinet door must remain closed for at least 5 seconds for the initialisation of

the optical tamper detectors to be completed.

Содержание FT Controller 3000

Страница 1: ...andI Ofunctionalityintoasingleproduct CardaxFTLocalBUS connectionsarenotsupported Reader Interface InterfacestoreadersandassociatedI Oaresetupasfourdistinctgroups numbered1to4 EachgroupisthesameandprovidesconnectiontoeitheroneWiegandortwoCardaxIV readers andfourbalanced 4 state inputsandtwogeneralpurposerelayoutputscapableof switching24voltsDC AC 5Aresistiveloads Eachgroupisalsoprovidedwitha12VDC ...

Страница 2: ...eapproximately0 5VDClowerthanthevoltagesupplied totheCardaxFTController3000 Thefusesareresettable i e underfaultconditions fuses gohighresistance Whenthefaultsubsidesorpowerisremoved thenthefuseswillcooland resetthemselves Thecurrentloadontheseconnectionpoints PA1toPA4 isinadditiontothe1 0Arequired bytheCardaxFTController3000 Whenusingtheseconnectionpoints ensurethePower SupplytotheCardaxFTControl...

Страница 3: ...nectedtoplugP3 Balanced Inputs Cablingshouldbeaminimumsizeof0 2mm2 24AWG forallinputs Toensurecorrecttamperdetection shortoropencircuit thebalancedinputsrequire4k7 ohmresistorstobeconnectedascloseaspossibleto thedevicebeingmonitored Whenthemonitoreddeviceincorporatesanormally closedtamperswitch itcanbewiredin serieswithresistorR1 Alarm sensor Input plug 4k7 GND 5 V R2 4k7 R1 4k7 RefertoChapter2oft...

Страница 4: ...ableclampsfittedintothebaseoftheCabinet Refertothenextsection Componentlayout forthelocationoftheplugs PA1 to PA4 Powerout PB1 to PB4 Readerports PC1 to PC4 Balancedinputs PD1 to PD4 Balancedinputs P1 Powerin P2 10BaseTEthernetport P3 Dial upRS232port P4 RS485 PE1 to PE4 Relayoutputs PF1 to PF4 Relayoutputs Remember Thebalancedinputsrequirethe4k7ohmresistorstobeconnectedasclose aspossibletothedevi...

Страница 5: ...UT VOUT VOUT VOUT PA4 PA3 PA2 PA1 2 1 2 1 2 1 2 1 PA4 POWER OUT PA3 POWER OUT PA2 POWER OUT PA1 POWER OUT COMB OUT2 COMA OUT1 DATA1 DATA1 DATA1 DATA1 DATA0 DATA0 DATA0 DATA0 PB4 PB3 PB2 PB1 2 3 1 4 2 3 1 4 2 3 1 4 2 3 1 4 COMA OUT1 COMA OUT1 COMA OUT1 COMB OUT2 COMB OUT2 COMB OUT2 2 3 1 IN2 IN2 IN2 IN2 GND IN1 IN1 IN1 IN1 PC4 PC3 PC2 PC1 2 3 1 2 3 1 2 3 1 GND GND GND IN4 IN4 IN4 IN4 GND IN1 IN1 IN...

Страница 6: ...normalrunningsequence Note Thesectiontitled RunLED laterinthischapter detailsthedifferentmeanings ofthevariousflashsequences 4 Set switch 2 to OFF open Dial up Serial setup details RefertotheDial up Null ModemInitialisationsectionofChapter23intheCardaxFT CommandCentreUserGuide fortheprocedure Optical tamper detectors ThefrontopticaltamperdetectorwillsensewhentheCabinetdoorisopened Therearopticalta...

Страница 7: ...startup themaincodedoesnotrun Instead thelocal configprogramattemptstoestablishconnectionviaserial COM port OFF On startup the main application e g B201b4 exe is run DS6 OFF Unused DS7 OFF Unused DS8 OFF Unused Dip Switch Settings ThefollowingtableshowstheDipSwitchSettings TheSettingsinboldspecifythedefault startupconfiguration Ethernet connection LEDs Component Function LEDwilllightwhen D9 LANAct...

Страница 8: ...d it has connected to the network 4flashes 4flashes pause Noprivatekeyorcertificateloaded eachflashis50mson 400ms seenotebelowforobtainingkeys offandthepauseis1 2s andcertificates 5flashes 5flashes pause Invalidprivatekeyorcertificateloaded eachflashis50mson 400ms orkeyandcertificatedonotmatchthe offandthepauseis1 2s CardaxFTControllerserialnumber 6flashes 6flashes pause The Cardax FT Controller h...

Страница 9: ...mbertolabeleachcableasyouremoveit 3 Removethe9xM3securingscrewsthatholdthePCBontotheCardaxFTCabinet fixingstandoffs 4 CarefullyliftthePCBclearoftheCabinet Replacing the PCB 1 To replacetheCardaxFTControllerPCB reversetheaboveprocedure Note YoumusttheninitialisetheCardaxFTController3000asdetailed earlierinthisInstallationNote Connector wiring Ethernet 10BaseT The10BaseTEthernetconnectstosocketP2via...

Страница 10: ...ththelimitsforaClassBdigital device pursuanttopart15oftheFCCRules Theselimitsaredesignedtoprovide reasonableprotectionagainstharmfulinterferenceinaresidentialinstallation Thisequipment generates uses andcanradiateradiofrequencyenergyand ifnotinstalledandusedin accordancewiththeinstructions maycauseharmfulinterferencetoradiocommunications However thereisnoguaranteethatinterferencewillnotoccurinapar...

Отзывы: