40
Output
Aux Out Type
– Auxiliary output type sets the use for the 24VAC auxiliary output signal. If a
powered exhaust is selected for this output, it will eliminate the option to control a powered
exhaust with a 0-10VDC signal.
VDC Out1
– Output #1 configures the use for OUT #1 on the “To RTU” side of the RTULink.
VDC Out2
– Output #2 configures the use for OUT #2 on the “To RTU” side of the RTULink.
VDC Out1
Range
– Output 1 range is the voltage range that the component connected to output
1 is designed to operate with. Once set, the RTULink will use the low-end voltage of this range
for an OFF signal and the high-end voltage of this range for a fully modulated ON signal.
VDC Out2
Range
– Output 2 range is the voltage range that the component connected to output
1 is designed to operate with. Once set, the RTULink will use the low-end voltage of this range
for an OFF signal and the high-end voltage of this range for a fully modulated ON signal.
Power Exhaust
– The powered exhaust threshold is the percentage open the economizer/damper must
be in order for the powered exhaust to turn on. For an ON/OFF powered exhaust, this is the threshold at
which it turns on. For a modulating powered exhaust, the speed of the exhaust will modulate linearly as
the economizer/damper opens from this threshold to fully open (100% open).
Enable Max HP
– Setting to enable or disable maximum heat pump runtime.
Max HP Runtime
– Time setting for heat pump runtime before auxiliary heat activates
Emer. Heat Lock
– Setting to enable or disable emergency heat.
Lockout Temp
– If the outside air temperature is above “Lockout Temp” setting, emergency heat will be
locked out.
Set Point Limit
– Setting to enable set point limit adjustments.
Limit SP Adjust
– This allows the user to change the current temperature set point through the home screen.
The range adjustment is 0-100 degrees.
Service
Password to enter factory menu is 1 2 3 4.
Temperatures
– User can monitor various temperature values.
Air %
– Displays outdoor and return air percentage.
RH Values
– User can monitor various RH values.
Open/Closed Status
– Menu to view the open/closed status of all inputs.
Inputs
– Allows user to monitor all of the variable input values.
Outputs
– Allows user to monitor all of the variable output values.
Clear Faults
– This will clear the entire fault history. If there is an active fault when cleared, that fault will show up
until it is fixed.
Set Clock
– Set day and time.
Time Zone
– Set time zone for the unit.
Factory Reset
– This will reset the board to factory commissioned settings.
Содержание RTULink
Страница 2: ...2...
Страница 12: ...12 Figure 10 Space Temperature RTULink Wiring Figure 9 Space Thermistor Detail Plastic Housing Wall Mount...
Страница 30: ...30 Main Board HMI Menu Tree...
Страница 31: ...31...
Страница 32: ...32...
Страница 33: ...33...
Страница 34: ...34...
Страница 41: ...41...
Страница 42: ...42...
Страница 43: ...43...
Страница 44: ...44...
Страница 52: ...52 APPENDIX C Fixed Dry Bulb Economizer Figure 34 Fixed Dry Bulb Economizer Operation...
Страница 53: ...53 Differential Dry Bulb Economizer Figure 35 Differential Dry Bulb Economizer Operation...
Страница 54: ...54 Fixed Enthalpy Economizer Figure 36 Fixed Enthalpy Economizer Operation...
Страница 55: ...55 Differential Enthalpy Economizer Figure 37 Differential Enthalpy Economizer Operation...