background image

 

 

7

 

   

 

 

Refrigerant jet noise

 

            Fault: a continuous noise like a water spray from the capillary. 

              Causation:  the  end  of  the  capillary  is  in  the  wrong  position,  or  there  are  rough  edges  on  the  end  of  the 

capillary. 

             

 

Solution :   

1>.  Heat  the  soldered  joint  of  the  capillary 

(Fig.3  showing  A  point)

,  then  remove  the  capillary  from  the 

evaporator and smooth the end with an eraser. (Caution: do not allow any particles into capillary unit). 

2>. Replace  the  capillary  into  the  evaporator,  then  solder  it  back  into  the  correct  position  (not  exceeding 

15mm in the evaporator) and pack the joint with anti vibration compound. 

3>. Vacuumize and recharge with refrigerant. See

 (

2)

 

 

 

     

 

Capillary vibration noise 

Fault: high frequency impact noise in capillary Zone. Caused by either 

              Causation:   

1>. The  capillary  being  insert  too  deep  into  the  evaporator,  so  when  the  refrigerant  is  Jetting,  the  end  of 

vibrating capillary will hit the inside of the evaporator. 

2>. Vibration from the capillary touching the inside of the cabinet or air duct board, then when refrigerant 

is jetting. 

    Solution:   

1>. If the capillary is inserted too deep, heat it with the solder, solder it again(Please noted, the deep inserted 

is not bigger than 15mm), and vacuumize it and add the refrigerant. 

(

2)

 

2>. If the capillary touch the inner cabinet or the air duct panel, adjust the position of the capillary and add 

the incabloc plastic. 

(Fig.3)

 

 

 

     

 

Oil jam noise 

              Fault: intermittent and deep jet noise coming from inside of the capillary. 

Causation:  Compressor  oil  flowing  into  the  cooling  system  pipe  work  probably  due  to  the  unit  leaning  during 

Fig. 6 

Fig. 6.1 

Содержание WI6225

Страница 1: ...WI6225 Caple 60cm 2 Door Wine Cabinet Technical information...

Страница 2: ......

Страница 3: ......

Страница 4: ...or 2 13 DG7 3 1 BH Evaporator fan 2 14 DG22 209 Air duct board 2 15 DG19 1 Fan cover 2 16 DG13 198 Senser cover 2 17 DG8 8 Senser 2 18 DG3 12 W LED Light 2 19 DG13 383 Display holder 2 20 DG20 256 Dis...

Страница 5: ...le 60cm 2 Door Wine Cabinet 33 DG14 167 BL Lower hinge module Left 1 34 DG12 91 2 Condenser 1 35 DG13 6 11 Cabinet leg 4 36 DG12 113 Air circulating pipe 2 37 DG22 80 2 Compressor bracket 1 38 DG14 56...

Страница 6: ......

Страница 7: ...ry protection well When servicing the wine cooler with R600a systems please make sure the ambient is well ventilated Preparation before maintenance Tools 1 Plier 2 Cross screwdraver 3 Assistant pipe 4...

Страница 8: ...cooler and check the current again check the discharge pipe of the compressor at the same time if it has an clear air pressure if the electricity is still too high or has not air pressure it shows th...

Страница 9: ...pressure pipeline is on the process pipe of the filter Apply the vacuum pump for approximately 20 minutes Until the vacuum is lower than 100Pa Then solder the process pipe of the filter Keep the the s...

Страница 10: ...ews need not to remove and remove the air duct board Be attention to unplug the connection wire when removing the air duct board You can move slowly aside until you can see the fans wire and unplug th...

Страница 11: ...ant pipe soldered jointed B Anti dew pipe soldered joint C Right zone suction pipe soldered joint D Discharge pipe soldered joint E Left zone suction pipe soldered joint F Condenser soldered joint G F...

Страница 12: ...the fan s fault the reason is following a The axletree of the fan broken b The bad balance because the fans abrasion 3 The fan can be replace with another same model s fan the procedure is following a...

Страница 13: ...ency impact noise in capillary Zone Caused by either Causation 1 The capillary being insert too deep into the evaporator so when the refrigerant is Jetting the end of vibrating capillary will hit the...

Страница 14: ...t fix for the door Fig 7 The instability of the wine cooler temperature The unstable temperature is caused by the evaporator fans cease and it can be check by the below method When the compressor is r...

Страница 15: ...ion wire and the main board whether short circuit if not replace the sensor with the same module See Fig 8 6 The LED display shows HI and it is the high temperature protection indication After running...

Страница 16: ...ht is normal and another zone is not cooling or over low temperature lower than the temperature preset 3 or one zone is not cooling the other zone is over cold please check the refrigerant valve 2 Tur...

Страница 17: ...trical box in right zone disconnect all connectors remove the main PCB The process of display PCB removed remove the shelves take apart the inner electrical box disconnect all connectors if necessary...

Страница 18: ...ers on display board supporter 8 as per arrowhead direction and then remove the display board and its two connectors from both sides Replace the display board See Fig 11 Fig 12 The name and explanatio...

Страница 19: ...compressor 7 To the valve 8 To the main PCB white 9 To the condenser fan Red 10 To the transformer secondary How to remove the power PCB and transformer The process of power PCB removed remove the el...

Страница 20: ...replace the LED light The process of LED light removed remove all shelve in the zone take apart the inner electrical box disconnect light connector if necessary remove the main PCB remove the LED ligh...

Отзывы: