
This fire is a very effective heating appliance and must be fitted against a wall of non-combustible material as
classified in BS 476-4:1970 (2007).
All parts of the appliance become hot while running and should therefore be considered to be working surfaces.
An air vent is not required for this application. The appliances have been tested without the need for additional
air requirements.
We recommend that if the chimney/flue has been used for solid fuel, it is swept prior to installation of this
appliance and that any flue restrictor or damper plate should be removed.
The chimney/flue must always generate a positive up draught to ensure safe operation.
The installer must then establish that all the products of combustion are entering the flue within ten minutes of
lighting from cold. This can be verified by inserting a lit smoke match into the central duct immediately above the
door. It should NOT be inserted into the left and right convector ducts.
This operation should be carried out before fitting the trim so no staining occurs (see ‘Spillage Test’ page 7).
An isolation valve must be fitted adjacent to the appliance. When closed, this will allow the complete burner and
control assembly to be disconnected for maintenance or repair in accordance with national regulations.
The gas supply should be provided by a semi rigid pipe with an 8mm diameter and should be no longer than 1.5
metres in length.
NOTE:
When the gas supply pipe is passed through masonry or other brickwork always ensure that the end
of the pipe is covered to avoid any debris passing through into the appliance controls. The pipe should be
sleeved and sealed with a suitable fire resistant non-setting mastic.
The appliance is fitted with an Oxygen Depletion Sensor (ODS) that monitors the room for products of
combustion. If products are detected, the ODS will automatically shut down the appliance. If this situation
arises, re-light the appliance, referring to the user instructions (page 24). If shut down re-occurs, a qualified
person must be called to thoroughly check the appliance.
The spillage monitoring system (ODS pilot) must not be put out of operation or be tampered with or adjusted
by either the installer or the user. If the unit is found to be at fault it should be replaced with the
manufacturers original replacement parts.
NOTES FOR THE INSTALLER AND END USER
6
Содержание Designline DL400
Страница 2: ......
Страница 33: ...9 10 7 8 11 SPLIT LOG LAYOUT DL700 DL800 CONTINUED 33 ...
Страница 38: ...SERVICE NOTES 38 ...
Страница 39: ...SERVICE NOTES 39 ...