Page 47
2 SP
Displays (and allows modification when logged in) the control panel
setpoints.
AcceptTime(Min)=
Time in minutes the acceptance voltage must be met before changing to float
charge mode. Default=120
Accept(V) =
The acceptance voltage that must be met before changing to float charge mode.
Default=14.4
BComp(mV/V/Vell)=
The battery temperature/charge voltage compensation set point. The compensation
temperature is based on the control panel atmospheric temperature. If the control
panel and battery bank experience differing temperatures set this to 0 (zero).
Default=-5
Connect(V)=
The load 1,2&3 low voltage reconnect voltage. Default=12.6
Default(1/0)
Resets the factory defaults for all setpoints if set to 1.
DiscDly(Sec)=
The time in seconds the battery voltage must remain below the Disc(V) setpoint
before disconnecting the low voltage disconnect circuits (if enabled). Default=300
Disconnect(V)=
The load 1,2&3 low voltage disconnect voltage (if enabled). Default=11.5
DiscDisab1(1/0)=
Disables or enables the low voltage disconnect for circuit #1. Default=1 (Disabled)
DiscDisab2(1/0)=
Disables or enables the low voltage disconnect for circuit #2. Default=1 (Disabled)
DiscDisab3(1/0)=
Disables or enables the low voltage disconnect for circuit #3. Default=1 (Disabled)
EqualTime(Min)=
The time in minutes to hold the equalize voltage (if started). Default=120
Equalize?(1/0)
If set to 1 this immediately starts the equalize process for the EqualTime(Min) setpoint
duration at the Equal(V) setpoint voltage. ONLY FOR LEAD ACID BATTERIES.
Equal(V)=
The target voltage during equalize charge mode (if enabled). Default=15.2
Float(V)=
The target voltage during float charge mode. Default=13.2
ValveAnaGain=
The measured time for the motorized valve to change from fully open to fully closed.
Value x 10 = time in seconds. Do not change unless using an alternate motorized valve
than supplied from the factory. Default=0.6 (6 seconds)
ValveMinimumPos=
Sets the minimum allowable valve position (%). Default=0
CurrentSpt=
Sets the maximum allowable generator current. Default=25
TurbnOffDly(Min)
The time in minutes to hold float state voltage before closing the motorized valve to
stop generation. Default=5
TurbnOnDly(Min)
The time in minutes the battery voltage must remain below the TurbineStart(V) setpoint
before opening the motorized valve to start generation. Default=1
TurbnCntl?(1/0)
Disables or enables the controller’s ability to adjust the motorized valve. Default=1
(Enabled)
TurbineStart(V)=
Low voltage set point at which the charge cycle begins. Default=11.9
Valve C/-/O 123=
Manually or automatically open and close the motorized valve. 1=closed,
2=automatic, 3=open. Default=2
3 LOGON
Log on to edit system setpoints. Enter code 1234-enter to edit the
setpoints. Once a code has been entered the setpoints in ‘2 SP’ can
be edited. Always use caution when editing system setpoints.
5 CLK
Shows and allows editing of the internal system clock.
7 LCD
Allows contrast adjustment for the LCD display (1-255)
8 I/O
Shows the status of the input and output circuits for the control
panel. A dot indicates an input/output not in use. A number
indicates an input/output in use.
Содержание M300 Pico
Страница 1: ...M300 Pico Hydro System Installation Operations Maintenance Version 2 0 0 1 ...
Страница 2: ...Page 2 ...
Страница 4: ...Page 4 ...
Страница 6: ...Page 6 ...
Страница 8: ...Page 8 ...
Страница 16: ...Page 16 ...
Страница 17: ...Page 17 4 Equipment Installation ...
Страница 29: ...Page 29 5 System Operation ...
Страница 36: ...Page 36 ...
Страница 37: ...Page 37 6 Maintenance ...
Страница 39: ...Page 39 7 Appendix ...
Страница 48: ...Page 48 7 4 Equipment Drawings and Performance Curves ...