12
Gas connection
12. Connect incoming gas supply pipe to
1
/
2
” compression fitting at rear
of appliance. For inlet position see figure 15.
Log installation
13. The burner is contained
within the burner cham-
ber. .Refer figure 16.
14. Carefully unpack the log set. Logs are numbered as follows:
No 1 - Left front log
No 2 - Left back log
No 3 - Right front log
No 4 - Right back log
Position the four individually numbered logs in the following order on
the burner head as shown in figures 17-20. The male locating pins in
the burner head must engage with corresponding holes in the indi-
vidual logs.
a) Place log No.1 onto the 2 front left
pins on the burner head, ensuring that
the charring faces the front. Refer figure
17.
b) Place log No.2 onto the 2 left back
pins. Refer figure 18.
c) Place log No.3 on single right front
pin, ensure fork locates over log
No. 2. Refer figure 19.
16
19
18
15
17
13
d) Place log No. 4 on single right back
pin, ensure left side of log rests on de-
pression in No. 3 log. Refer figure 20.
15. Refit the inner glass, but do not overtighten
the screws.
16. Refit the heater front.
Gas control
17. Gas control layout is as indicated in figure 21.
Operate the heater on HIGH and LOW burner on all fan speeds. The
flame should be stable, no lifting from the burner and the logs should
glow after approximately 15 minutes of operation on HIGH burner.
If the flame is unstable:
• Check that the burner is located correctly.
• Check that the glass front is located correctly and is against the
sealing rope.
• Check that the gas pressure is correctly adjusted.
If the heater still does not operate to specification refer to the trouble-
shooting chart on pages 20 & 21, or contact Sampford IXL in your
state.
Pressures for ‘Burner full on’ and ‘Burner low flame’ are factory
set, however if pressures need to be checked or adjusted follow the
procedures described below and on the next two pages.
To check control outlet pressure at burner ‘Full on” and ‘Low Flame”
positions remove the plastic cap from the regulator adjustment location
as indicated in figures 22 (a) & (b).
20
21
Advise the user in the
operation of the heater.
Important:
To achieve the correct
visual flame effect:
On Propane the gas
pressure must be set at
2.65 kPa with burner
operating on maximum
setting.
On Natural Gas the gas
pressure must be set at
0.75 kPa.