
7
5. To increase the fan speed to MED, press switch for MED set-
ting. Refer figure 5.
6. To increase the fan speed to HIGH, press switch for HIGH
setting. Refer figure 6.
7. To turn the burner to LOW setting, press switch for LOW set-
ting. Refer figure 7.
On low burner setting it is more efficient to operate the fan
speed on LOW.
8. If the burner fails to ignite, wait 20 seconds and repeat the
ignition porcedure. See below.
To turn burner OFF
To turn burner ON
5
6
7
14
This heater is a flued appliance. It must be properly connected to a
flue system in accordance with the latest edition of the Gas Installa-
tion Code, AS 5601/AG 601.
If elbows are needed, the total horizontal length depends on the
number of elbows used. Venting should never slope down. A 6mm
per 500mm horizontal rise is recommended.
If practical locate the heater in a position to minimise the use of
horizontals and elbows.
The flue rise should be a minimum of 1.8m before any horizontal
run is used.
If placed against a combustible wall the 40mm rear spacers locate
against the wall.
1. Ensure clearances to combustible have been observed. For
clearances refer page 10.
2. The centre line of the flue is 75mm to rear of appliance (ex
cluding rear spacers).
3. Carry out installation as per figure 23 (ceiling plate installation)
and figure 24 (flue installation).
Cut a hole 180mm ø in the ceiling in line with the flue position.
Secure ceiling plate against the ceiling by bending out the tabs
above the ceiling.
Note: If the ceiling has an incline, the ceiling box will need to
be fitted. Installation instructions are supplied with the ceiling
box.
The flue kit contains:
3 x 900mm lengths of 125mm ø painted flue.
1 x 900mm length of 125mm ø plain flue.
1 x ceiling plate
1 x 900mm painted bottom flue spigot.
20
23
Flue installation
Flue kit