SYSTEM 2316E/2316EC Installation Manual
Command Location 27: Soft Zone A (Emergency)
(1)
(2)
(3)
(4)
0
0
1
4
Default Values
2
7
Digit Positions (1) and (2): Emergency Report Code
Program 00 to disable alarm reporting for Emergency zone.
Digit Position (3): Emergency Zone Receiver Select
0 = Receiver 1 with Receiver 2 as backup
1 = Receiver 1 only
2 = Receiver 2 only
3 = Receiver 1 and Receiver 2 (Dual Reporting)
Digit Position (4): Emergency Loop Bell Type
1 = 3-pulse temporal
2 = Pulsing
3 = Steady
4 = Chirp
Command Location 28: Soft Zone B (Fire)
(1)
(2)
(3)
(4)
0
0
1
1
Default Values
2
8
Digit Positions (1) and (2): Fire Report Code
Digit Position (3): Fire Receiver Select
Digit Position (4): Fire Loop Bell Type
A
B
C
D
E
F
Hexadecimal Value
Key Strokes
0
1
2
3
4
5
PROGRAMMING CONVERSIONS
CL 27 - 29
Command Location 29: Soft Zone C (Police)
(1)
(2)
(3)
(4)
0
0
1
3
Default Values
2
9
Digit Positions (1) and (2): Police Report Code
Digit Position (3): Police Zone Receiver Select
Digit Position (4): Police Loop Bell Type
Refer to CL 27 for information
about programming this zone.
Refer to CL 27 for information about
programming this zone.
This Zone is identified by the "E" key
on the Alpha and LED Plus keypads.
This Zone is identified by the "F" key
on the Alpha and LED Plus keypads.
This Zone is identified by the "P" key
on the Alpha and LED Plus keypads.
NOTE:
Command Location 2F Digit Position (4) must
be programmed to YES to enable Soft Zones.
5 = Silent