C&D Technologies DCS-100HIT Скачать руководство пользователя страница 9

was 2.25 v/c, the ground fault would be 
approximately 60 cells (ten 12 volt units) from
the battery system output terminal.

Battery System

Float Charging Current

If the DC float current can be measured, it can
provide an indication of the proper current 
acceptance of the battery system. Depending on
the charging voltage per string and the temperature,
the float current per string should be approximately
that shown in Figure 3. The float current will 
approximately double for each 18°F (10°C)
above 77°F (25°C).

If the DC float current is zero there is an open
circuit in the battery string. If the float current is
higher than anticipated, it may be due to elevated
temperature of the battery or shorted cells within
the string. In either case the cause should be 
determined and corrected. Elevated temperatures
and shorted cells are both situations which can
lead to thermal runaway.

Individual Battery

Float Charging Voltage

While the battery string may be charged at an
average of between 2.25 and 2.3 volts per cell,
ot all cells will float at the exact average voltage.
Each cell has a somewhat different impedance
and rate of oxygen recombination and will therefore
exhibit a slightly different float voltage at the
same float current. For example, all the 12 volt
batteries in a string charged at 2.3 volts per cell

will not float at 13.8 VDC but may vary from 13.3
to 14.5 and still be normal. If the system is equalized
for 24 hours upon installation, or after with an 
extended time in float service, this spread in float
voltage will normally decrease.

Refer to table 1, Electrical Characteristics, for
each series battery as listed in the documents
noted in the table of contents, which lists the 
minimum and maximum DC float voltages to be
measured across batteries in a series string. If an
individual battery measures too low, it may be an
indication of a shorted cell. 

If an individual unit measures too high, it may be
an indication of increased resistance within the
cell. If one unit measures very high while the 
balance of the units in the string indicate near the
open circuit value, the high voltage cell may have
an open circuit.

Shorted cells within the string will lead to 
increased voltage applied to the remaining 
good cells in the string and higher float current.
For example, a 24 cell string charging at 55.2
VDC (2.3 v/c) which has 2 shorted cells will be
charging the remaining 22 cells at 2.5 v/c 
(55.2 VDC/22 cells) and the resulting increase 
in float current is sure to result in eventual 
thermal runaway.

A battery with a shorted or open cell can usually
be confirmed by comparing the impedance of the
individual units or by comparing the AC ripple 
voltage measured across the individual units.

DO NOT perform a high rate load test on batteries
that are suspected of having a shorted or open
cell. This would be hazardous since a spark 
internal to the cell could ignite the internal gases.

A battery suspected of having a shorted or open
cell should be removed and replaced immediately.

More information concerning the measurement
and interpretation of individual battery float 
voltages is contained in the Technical Bulletin 
"Integrity Testing" #41-7264.

0

1

2

3

4

5

2.15

2.2

2.25

2.3

2.35

2.4

2.45

2.5

M

ill

ia

m

pe

re

 F

lo

at

 C

ur

re

nt

 P

er

 A

m

pe

re

 H

ou

r C

ap

ac

ity

Figure 3 - Float Current Vs. Voltage

Figure 3-Float Current Vs. Voltage

41-7546/0213/CD                                                                                           9                                                                                        www.cdtechno.com

Содержание DCS-100HIT

Страница 1: ...Valve Regulated Lead Acid Battery 20 to 200 ampere hours capacity 10 Year VRLA Battery Periodic Maintenance Instructions 41 7546 TECHNICAL BULLETIN 41 7546 0213 CD www cdtechno com...

Страница 2: ...and Battery Temperature 7 Battery Visual Inspection 7 System Float Voltage 8 Ground Fault Check 8 Float Charging Current 9 Individual Battery Float Voltage 9 High Rate Momentary Load Test 10 Battery...

Страница 3: ...acity of the sum of the capacities of the individual strings The 10 Year VRLA battery is a lead acid battery which facilitates an oxygen recombination cycle The net result is that under normal conditi...

Страница 4: ...e battery system Disposal Lead acid batteries are to be recycled Batteries contain lead and dilute sulfuric acid Dispose of in accordance with Federal State and local regulations Do not dispose of in...

Страница 5: ...loat voltage 6 Momentary high rate load test 7 Battery system capacity test A test of the individual unit resistance impedance or conductance while optional is also recommended on a periodic basis Thi...

Страница 6: ...atteries are functional 4 Optionally measure and record the resistance impedance conductance of the individual units to trend the condition of the individual units over time and to detect dramatic dif...

Страница 7: ...n short circuits or ground faults When batteries are cleaned they should be on open circuit For cleaning use a cloth moistened in a solution of bicarbonate of soda and water Do not use cleaners of unk...

Страница 8: ...ates may have occurred and the battery may have to be replaced Extended overcharging will cause excessive float current corrosion of the plate grids gassing and drying of the limited amount of electro...

Страница 9: ...acteristics for each series battery as listed in the documents noted in the table of contents which lists the minimum and maximum DC float voltages to be measured across batteries in a series string I...

Страница 10: ...of this data can indicate string uniform gradual degradation and loss of capacity with time This is shown in Figure 4 Rapid changes in individual units may indicate shorted open and drying cells and...

Страница 11: ...replacement is when it no longer supports the load for the minimum required time even if the battery is still greater than 80 of rating However even at minimal load the battery should not remain in s...

Страница 12: ...d develop thermal runaway internal arcing could result in explosion Heat the battery Run parallel cables Add required parallel strings Replace isolated units with shorts and evaluate entire string Ele...

Страница 13: ...rmal runaway possibly caused by high temperature environment overcharging excessively high recharge current shorted cells or a ground fault or a combination of these items Could result in the emission...

Страница 14: ...eal that is attacking the interunit connector Increased connection resistance and resulting increase in the connection heating and voltage drop at high rate discharge Disassemble connection clean coat...

Страница 15: ...y Equalization and boost charging will be less effective and will require extended time If possible reset the charger output voltage to the recommended value or accept longer equalization time Individ...

Страница 16: ...of the value of the DC float voltage Poor filtering of the charger output Excessive AC ripple could cause the battery to cycle at the ripple frequency and result in heating and deterioration of the p...

Страница 17: ...time Fully recharge the battery AC ripple current exceeds 5 amperes per 100 Ah rated battery capacity Poor filtering of the charger Excessive AC ripple current will result in battery heating reduced...

Страница 18: ...battery or replace as required Connection resistance increase of 20 or more from original value Repetitive cycles resulting in heating and cooling of connection can result in relaxation of torque and...

Страница 19: ...TEL12 70 Inserted 1 4 20 110 12 84 13 5 13 8 245 9 3 8 0 0050 1326 TEL12 80 SLC Inserted 1 4 20 110 12 84 13 5 13 8 283 10 4 4 0 0040 1467 TEL12 90 Inserted 1 4 20 110 12 84 13 5 13 8 331 11 5 0 0 003...

Страница 20: ...sion by C D Technologies Inc without notice While such information is believed to be accurate as indicated herein C D Technologies Inc makes no warranty and hereby disclaims all warranties express or...

Отзывы: