C&D Technologies DCS-100HIT Скачать руководство пользователя страница 10

High Rate Momentary Load Test

The high rate momentary load test is a functional
test of the individual battery within the series
string. It does not replace a capacity test but it
does indicate if the battery is functional at least
up to the ampere capability of the test load. 
A typical load used for batteries in the 30 to 600
ampere range is 100 amperes. The voltage of
the unit 10 seconds after application of the test
load should be at least 1.7 v/c average (10.2,
5.1, 3.4,and 1.7 VDC) for 12, 6, 4 and 2 volt 
batteries respectively) or the battery should be
suspected of being open, shorted, discharged or
of very high resistance and low capacity.

Never

perform the high rate momentary load 

test on a battery suspected of having a shorted
or open cell. Full face protection should always
be worn during this test, since a spark internal 
to a cell could ignite the residual gasses within
the cell.

More information concerning this test and 
the minimum voltages to be expected by part
number is contained in the Technical Bulletin
"Integrity Testing" #41-7664.

Impedance Testing

The normal wear out mode of the VRLA 
battery includes corrosion of the plate grids, 
deterioration of the plate active material and
some drying of the electrolyte. Abnormal failure
modes would include deterioration of the 
conductive path and excessive drying of the
electrolyte. These processes will all increase the
resistance of the affected cells and periodic
measurement of the impedance, resistance or
conductance of the cells and trending of this data
can indicate string uniform gradual degradation
and loss of capacity with time. This is shown in
Figure 4.

Rapid changes in individual units may indicate
shorted, open and drying cells and cells with 
deteriorating conductive paths.

individual units in the string proportional to their
relative resistance. Therefore in the absence of
an impedance, resistance or conductance test
set, the AC ripple voltage across the individual
units can be measured with a DVM and compared
to each other and the norm as an indication of
their relative resistance and condition.
If the resistance of the batteries has increased by
30% over that when it was new, the battery
should be further tested to determine the cause
and if necessary the battery or system should be
capacity tested to assure reliability.
More information on this topic is contained in the
Technical Bulletin "Impedance and Conductance
Testing" #41-7271.

Interunit Connecting Resistance

High resistance in the interunit connections and
loose connecting hardware can cause excessive
voltage drop during discharge resulting in reduced
operating time and in the extreme case even
cause melting of the battery terminals and 
potentially a fire.

The contacting surfaces of all connections should
be brushed clean, removing all lead oxide and
contamination, protected with a special 
antioxidation grease, and tighten.

70

80

90

100

110

120

130

140

0

10

20

30

40

50

60

70

80

90

100

%

 O

rig

in

al

 V

al

ue

   

 

% LIFE 

0

25

50

75

100

0

10

20

30

40

50

60

70

80

90

100

%

 ra

te

ca

pa

ci

ty

  

Figure 4 - VRLA Battery Impedance and

Conductance Vs. Capacity and Age

When an AC ripple voltage appears across a
string of batteries it will be subdivided across the 

41-7546/0213/CD                                                                                          10                                                                                        www.cdtechno.com

Содержание DCS-100HIT

Страница 1: ...Valve Regulated Lead Acid Battery 20 to 200 ampere hours capacity 10 Year VRLA Battery Periodic Maintenance Instructions 41 7546 TECHNICAL BULLETIN 41 7546 0213 CD www cdtechno com...

Страница 2: ...and Battery Temperature 7 Battery Visual Inspection 7 System Float Voltage 8 Ground Fault Check 8 Float Charging Current 9 Individual Battery Float Voltage 9 High Rate Momentary Load Test 10 Battery...

Страница 3: ...acity of the sum of the capacities of the individual strings The 10 Year VRLA battery is a lead acid battery which facilitates an oxygen recombination cycle The net result is that under normal conditi...

Страница 4: ...e battery system Disposal Lead acid batteries are to be recycled Batteries contain lead and dilute sulfuric acid Dispose of in accordance with Federal State and local regulations Do not dispose of in...

Страница 5: ...loat voltage 6 Momentary high rate load test 7 Battery system capacity test A test of the individual unit resistance impedance or conductance while optional is also recommended on a periodic basis Thi...

Страница 6: ...atteries are functional 4 Optionally measure and record the resistance impedance conductance of the individual units to trend the condition of the individual units over time and to detect dramatic dif...

Страница 7: ...n short circuits or ground faults When batteries are cleaned they should be on open circuit For cleaning use a cloth moistened in a solution of bicarbonate of soda and water Do not use cleaners of unk...

Страница 8: ...ates may have occurred and the battery may have to be replaced Extended overcharging will cause excessive float current corrosion of the plate grids gassing and drying of the limited amount of electro...

Страница 9: ...acteristics for each series battery as listed in the documents noted in the table of contents which lists the minimum and maximum DC float voltages to be measured across batteries in a series string I...

Страница 10: ...of this data can indicate string uniform gradual degradation and loss of capacity with time This is shown in Figure 4 Rapid changes in individual units may indicate shorted open and drying cells and...

Страница 11: ...replacement is when it no longer supports the load for the minimum required time even if the battery is still greater than 80 of rating However even at minimal load the battery should not remain in s...

Страница 12: ...d develop thermal runaway internal arcing could result in explosion Heat the battery Run parallel cables Add required parallel strings Replace isolated units with shorts and evaluate entire string Ele...

Страница 13: ...rmal runaway possibly caused by high temperature environment overcharging excessively high recharge current shorted cells or a ground fault or a combination of these items Could result in the emission...

Страница 14: ...eal that is attacking the interunit connector Increased connection resistance and resulting increase in the connection heating and voltage drop at high rate discharge Disassemble connection clean coat...

Страница 15: ...y Equalization and boost charging will be less effective and will require extended time If possible reset the charger output voltage to the recommended value or accept longer equalization time Individ...

Страница 16: ...of the value of the DC float voltage Poor filtering of the charger output Excessive AC ripple could cause the battery to cycle at the ripple frequency and result in heating and deterioration of the p...

Страница 17: ...time Fully recharge the battery AC ripple current exceeds 5 amperes per 100 Ah rated battery capacity Poor filtering of the charger Excessive AC ripple current will result in battery heating reduced...

Страница 18: ...battery or replace as required Connection resistance increase of 20 or more from original value Repetitive cycles resulting in heating and cooling of connection can result in relaxation of torque and...

Страница 19: ...TEL12 70 Inserted 1 4 20 110 12 84 13 5 13 8 245 9 3 8 0 0050 1326 TEL12 80 SLC Inserted 1 4 20 110 12 84 13 5 13 8 283 10 4 4 0 0040 1467 TEL12 90 Inserted 1 4 20 110 12 84 13 5 13 8 331 11 5 0 0 003...

Страница 20: ...sion by C D Technologies Inc without notice While such information is believed to be accurate as indicated herein C D Technologies Inc makes no warranty and hereby disclaims all warranties express or...

Отзывы: