Symptom

CAPACITY TEST
RESULTS

TEMPERATURE
CHECKS

Reduced operating
time at 77°F 
with smooth voltage
decline.

Normal wear out

Eventual failure to
support the load 
followed by potential 
for shorted cells.

Replace battery system
when at 80% of rated
capacity or before.

Reduced operating
time at 77°F with
step voltage decline
or voltage plateaus.

Individual low
capacity cells.

Reversed cells during
discharge-reversed cells
will become very hot
and will not fully recharge.

Replace the isolated
low capacity batteries.

Excessive initial 
voltage drop even to
the point of dropping
load in the first 
several seconds.

Battery is cold.
Cabling is too small.
High resistance 
connections.
Battery is undersized.
Shorted cells.

Excessive voltage drop.

Excessive voltage drop.

Cells will become hot,
could develop thermal
runaway; internal arcing
could result in explosion.

Heat the battery.
Run parallel cables.
Add required parallel
strings.
Replace isolated units
with shorts and evaluate
entire string.

Elevated battery
temperature.

Elevated room
temperature.
Inadequate cabinet
ventilation.

Discharge-Charge
cycle

AC ripple current
greater than 5 
amperes
rms/100Ah battery
capacity.

Reduced life and 
potential thermal 
runaway.

Reduced life and 
potential thermal 
runaway.

Can be normal if not
exceeding 18°F (10°C)
increase.
Reduced life and 
potential thermal 
runaway.

Improve room air
conditioning.

Improve cabinet 
ventilation and 
temperature.

Limit recharge current.

Determine cause of
excessive AC ripple 
current and correct.

Possible Causes

Possible Result

Corrective Actions

Elevated room
temperature.

Lack of adequate air
conditioning/ventilation.

Reduced battery life.

Cool the room or 
accept reduced 
battery life.

TABLE 1-VRLA Battery Symptoms and Solutions

41-7546/0213/CD                                                                                           12                                                                                         www.cdtechno.com

Содержание DCS-100HIT

Страница 1: ...Valve Regulated Lead Acid Battery 20 to 200 ampere hours capacity 10 Year VRLA Battery Periodic Maintenance Instructions 41 7546 TECHNICAL BULLETIN 41 7546 0213 CD www cdtechno com...

Страница 2: ...and Battery Temperature 7 Battery Visual Inspection 7 System Float Voltage 8 Ground Fault Check 8 Float Charging Current 9 Individual Battery Float Voltage 9 High Rate Momentary Load Test 10 Battery...

Страница 3: ...acity of the sum of the capacities of the individual strings The 10 Year VRLA battery is a lead acid battery which facilitates an oxygen recombination cycle The net result is that under normal conditi...

Страница 4: ...e battery system Disposal Lead acid batteries are to be recycled Batteries contain lead and dilute sulfuric acid Dispose of in accordance with Federal State and local regulations Do not dispose of in...

Страница 5: ...loat voltage 6 Momentary high rate load test 7 Battery system capacity test A test of the individual unit resistance impedance or conductance while optional is also recommended on a periodic basis Thi...

Страница 6: ...atteries are functional 4 Optionally measure and record the resistance impedance conductance of the individual units to trend the condition of the individual units over time and to detect dramatic dif...

Страница 7: ...n short circuits or ground faults When batteries are cleaned they should be on open circuit For cleaning use a cloth moistened in a solution of bicarbonate of soda and water Do not use cleaners of unk...

Страница 8: ...ates may have occurred and the battery may have to be replaced Extended overcharging will cause excessive float current corrosion of the plate grids gassing and drying of the limited amount of electro...

Страница 9: ...acteristics for each series battery as listed in the documents noted in the table of contents which lists the minimum and maximum DC float voltages to be measured across batteries in a series string I...

Страница 10: ...of this data can indicate string uniform gradual degradation and loss of capacity with time This is shown in Figure 4 Rapid changes in individual units may indicate shorted open and drying cells and...

Страница 11: ...replacement is when it no longer supports the load for the minimum required time even if the battery is still greater than 80 of rating However even at minimal load the battery should not remain in s...

Страница 12: ...d develop thermal runaway internal arcing could result in explosion Heat the battery Run parallel cables Add required parallel strings Replace isolated units with shorts and evaluate entire string Ele...

Страница 13: ...rmal runaway possibly caused by high temperature environment overcharging excessively high recharge current shorted cells or a ground fault or a combination of these items Could result in the emission...

Страница 14: ...eal that is attacking the interunit connector Increased connection resistance and resulting increase in the connection heating and voltage drop at high rate discharge Disassemble connection clean coat...

Страница 15: ...y Equalization and boost charging will be less effective and will require extended time If possible reset the charger output voltage to the recommended value or accept longer equalization time Individ...

Страница 16: ...of the value of the DC float voltage Poor filtering of the charger output Excessive AC ripple could cause the battery to cycle at the ripple frequency and result in heating and deterioration of the p...

Страница 17: ...time Fully recharge the battery AC ripple current exceeds 5 amperes per 100 Ah rated battery capacity Poor filtering of the charger Excessive AC ripple current will result in battery heating reduced...

Страница 18: ...battery or replace as required Connection resistance increase of 20 or more from original value Repetitive cycles resulting in heating and cooling of connection can result in relaxation of torque and...

Страница 19: ...TEL12 70 Inserted 1 4 20 110 12 84 13 5 13 8 245 9 3 8 0 0050 1326 TEL12 80 SLC Inserted 1 4 20 110 12 84 13 5 13 8 283 10 4 4 0 0040 1467 TEL12 90 Inserted 1 4 20 110 12 84 13 5 13 8 331 11 5 0 0 003...

Страница 20: ...sion by C D Technologies Inc without notice While such information is believed to be accurate as indicated herein C D Technologies Inc makes no warranty and hereby disclaims all warranties express or...

Отзывы: