Auxillary Outputs
Remote Start Switch 1
Immediately
Remote Start Switch 1 Hold
AUX Relay 1 Duration Regeneration
AUX Relay 2 Chemical Pump
Auxillary
Outputs
Remote Start
RS OFF
RS ON Immediately
RS ON Delay
10 Min
RS ON Hold
RS Value
2
SEC
ADVANCED PROGRAMMING
AUXILIARY OUTPUTS
From the Advanced Settings menu, press the UP / DOWN button to highlight the Auxiliary Output menu icon. Press the SET button to enter.
REMOTE START SWITCH 1 AND 2
There are 2 inputs for remotely starting a regeneration. One input is reserved for an external switch like a push button wired to a control panel as an
example. The second input is reserved for an input signal from other devices such as a pressure switch that could signal a regeneration.
RS OFF is the default value. RS ON Immediately would signal a regeneration as soon as the remote button or switch is pushed. RS ON Delay would
signal a regeneration to start at the end of the delay period. RS ON Hold would signal a regeneration when the remote button or switch is pushed
and held on for the RS Value.
AUX RELAY 1 & 2
There are 2 programmable outputs controlled from the start of a regeneration. The default is OFF.
ON Duration Regeneration would open the relay output signal at the start of a regeneration.
Up to 4 steps may be programmed in this mode.
In the On Cycle option you can select which cycles the relay output signal should be on for. All, some, or none of the cycles can be selected.
On for Chemical Pump or Product Water Polish may be selected to designate the relay to control these options.