.9.

.8.

CAUTION 

Risk of electric shock from energy stored in the inverter's capacitors. 
Do not remove cover until five (5) minutes after disconnecting all sources 
of supply have passed, and this can only be done by a service technician. 
The warranty may be voided if any unauthorized removal of cover occurs.

The inverter has been constructed according to applicable safety and technical guidelines. 

Use the inverter in installations that meet the following requirements ONLY:

       1).  The inverter must be permanently installed.

       2).  The electrical installation must meet all the applicable regulations and standards.

       3).  The inverter must be installed according to the instructions stated in this manual.

       4).  The system design must meet inverter specifications.

To start-up the inverter, the Grid Supply Main Switch (AC) must be turned on, BEFORE the DC 

Switch is turned on. To stop the inverter, the Grid Supply Main Switch (AC) must be turned off 

before the DC Switch is turned off.

2.3 Notice for use

3.1 Environmental considerations

3.1.1 Select a location for the inverter

When selecting a location for the inverter, consider the following:

●  The temperature of the inverter heat-sink can reach 167

°

F.

●  The inverter is designed to work in an ambient temperature range between -13~140

°

F.

●  If multiple inverters are installed on site, a minimum clearance of 20 inches should be kept 

    between each inverter and all other mounted equipment. The bottom of the inverter should be 

    at least 20 inches above of the ground or floor (see Figure 3.1). 

●  The LED status indicator lights and the LCD located on the inverter's front panel should not be 

     blocked.

●  Adequate ventilation must be present if the inverter is to be installed in a confined space.

Figure 3.1 Distances required between inverters

NOTE

 

Nothing should be stored on or placed against the inverter.

3. Installation

2.4 Protection Circuitry and Controls

2. Important Safety Instruction

      

  

 WARNING:

 Risk of fire

 

Despite careful construction, electrical devices can cause fires.

   Do not install the inverter in areas containing highly flammable materials or 

   gases.

   Do not install the inverter in potentially explosive atmospheres. 

20in

20in

20in

20in

40

in

To meet relevant codes and standards, the Canadian Solar U.S. three phase inverter line is 

equipped with protective circuitry and controls.  These include Arc Fault Circuit Interrupter 

(AFCI) and Anti-Islanding Protection.

Arc Fault Circuit Interrupter AFCI:

  

       Edition 2011 of the National Electrical Code®, Section 690.11, requires that all PV plants 

       attached to a building are fitted with a means of detecting and interrupting serial electric 

       arcs in the PV wiring and array. An electric arc with a power of 300W or greater must be 

       interrupted by the AFCI in the time specified by UL 1699B. A triggered AFCI fault may only 

       be reset manually. After clearing the source of the fault, the AFCI can be deactivated via 

       the inverter front panel interface.

Anti-Islanding Protection: 

       Islanding is a condition where the inverter continues to produce power even when the grid 

       is not present.  Circuitry, along with firmware, has been designed to determine if the grid is 

       present by adjusting the output frequency of the inverter.  In the case of a 60Hz resonant 

       system where the inverter is partially isolated from the grid, the inverter programming can 

       detect if there is a resonant condition or if the grid is actually present.  It can also 

       differentiate between inverters operating in parallel and the grid.

Содержание CSI-75K-T480GL03-U

Страница 1: ...com Customer Support Email service ca csisolar com This manual is subject to change without prior noti cation Copyright is reserved Duplication of any part of this issue is prohibited without written...

Страница 2: ...equipment has supplied The customer is fully liable for any modifications made to the system therefore any hardware or software modification manipulation or alteration not expressly approved by the ma...

Страница 3: ...ck mounting 3 4 Electrical Connections 17 18 3 4 1 Grounding 20 3 4 2 Connect PV side of inverter 22 3 4 3 Connect grid side of inverter 26 4 Communication Monitoring 6 5 1 Set Time 39 6 5 2 Set Addre...

Страница 4: ...ser manual 16 for 75K 18 for 80K 20 for 90 100 K 4 4 4 1 1 2 3 4 6 5 4 Hexagon bolt M10 40 LED lights LCD display 4 buttons Figure 1 2 Bottom view DC Switch AC output DC input AC Switch Vent COM COM M...

Страница 5: ...kaging regularly If packing is damaged wet pest damages etc repackage the inverter immediately Store inverters on a flat hard surface not inclined or upside down After 100 days of storage the inverter...

Страница 6: ...tilation must be present if the inverter is to be installed in a confined space Figure 3 1 Distances required between inverters NOTE Nothing should be stored on or placed against the inverter 3 Instal...

Страница 7: ...quite high 3 2 Product handling Figure 3 3 Handles used to move the inverter shown circled in red 3 1 2 5 Air circulation Do not install in small closed rooms where air cannot freely circulate To prev...

Страница 8: ...ical connections downward The steps to mount the inverter are listed below 1 Refer to Figure 3 6 drill holes for mounting screws based on the hole diameter of bracket using a precision drill keeping t...

Страница 9: ...install the inverter vertically If the inverter cannot be mounted vertically it may be mounted at angles greater than 15 degrees off horizontal Inverter cannot be mounted flat Vertical 15 Backward Fi...

Страница 10: ...the inverter are described below in table 3 1 All electrical connections must be in accordance with local or national standard Table 3 1 Electrical connections Parts Connection Cable size Torque DC te...

Страница 11: ...grounding terminal on the heatsink described below 1 It is recommended to use copper wire for the chassis ground Either solid conductor or stranded wire is acceptable Refer to local code standard for...

Страница 12: ...n see figure 3 23 Figure 3 18 Disassemble the Connector Cap nut Figure 3 19 Insert the Wire into the Connector Cap nut and contact pin Crimping plier Figure 3 22 Multimeter measurement Figure 3 23 Con...

Страница 13: ...he inverter Confirm proper string length and voltage range before connecting DC cable to the inverter NOTE The AC output neutral is not bounded to the ground The neutral wire is not necessary for the...

Страница 14: ...on box cover Figure 3 27 2 Strip the insulation of the wire past the cable crimping area of the OT terminal then use a hydraulic crimp tool to crimp the terminal The crimped portion of the terminal mu...

Страница 15: ...al 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 R S 4 8 5 A R S 4 8 5 B Use the network wire stripper to strip the insulation layer off the communication cable Using the standard wire sequence referenced in TIA EI...

Страница 16: ...e 4 8 System Work mode Network Manual Restart Reset Upgrade Device information Type SN Firmware version Current tiom Time zone Embedded Ethernet 1909583738 ME 121001 V1 0 6 20200612800 Fri Nov 06 2020...

Страница 17: ...by changing laptop to new IP address in range of inverter IP address and navigate to new inverter IP address System Work mode Network Manual Restart Reset Upgrade Obtain IP address automatically Save...

Страница 18: ...elect ENTER There are 4 sub menu options use the UP DOWN arrows to highlight ADVANCED SETTINGS Press enter to select 2 The screen will show that a password is required The default password is 0010 pre...

Страница 19: ...d do not have an array connection to ground Any measurement of a fixed voltage between ground and either the positive or negative string wiring indicates a leakage ground fault to ground and must be c...

Страница 20: ...w are followed in the exact order outlined 1 Select Grid Off in the Advanced Setting of Inverter LCD 2 Turn off the AC Switch between Canadian Solar inverter and Grid 3 Wait approximately 30 seconds d...

Страница 21: ...ode DRM NO Shows DRM Number I_DC01 Shows input 01 current value I_DC02 Shows input 02 current value I_DC20 Shows input 20 current value VPV_Total 1000 0V IPV_Total 99 0A V_A 345 7V I_ A 109 0A V_C 345...

Страница 22: ...move the cursor press up to select the number After enter the correct password the Main Menu will display a screen and be able to access to the following information 41 40 6 6 3 Version The screen sho...

Страница 23: ...e is fixed 6 6 7 Daily Records The screen shows history of changing settings Only for maintance personel 43 42 6 7 Advanced Settings Technicians Only NOTE To access to this area is for fully qualified...

Страница 24: ...166 V 244 2S V 166 0 16S 60 5Hz F 62Hz 2S F 2Hz 6 0 16S 57Hz F 59 5Hz 2S 57Hz F 0 16S 480V Rated L L 45 44 6 7 2 Grid ON OFF This function is used to start up or stop the power generation of Canadian...

Страница 25: ...DOWN key to move the cursor Press the UP key to revise the value Press the ENTER key to execute the setting Press the ESC key to return to the previous menu 6 7 7 Special Settings This function is app...

Страница 26: ...t 305V Figure 6 22 Volt VAR Voltage1 242V Voltage2 273V 1 NULL Description Inverter is not under any working mode 49 48 YES ENT NO ESC Power Factor 1 00 Figure 6 23 Fixed PF Figure 6 24 PF Range 4 Fix...

Страница 27: ...n working modes 1 NULL 2 Volt watt 3 Volt Var 4 Fixed PF 5 Reac power 6 Power PF 7 VgWatt UL 6 7 8 1 2 With Rule21 Standard selected NOTE The other three working mode P1 V Watt P1 V Var and P1 V P V Q...

Страница 28: ...ault value is PF 1 53 52 5 Reac power Not Required Description Inverter will generate reactive power based on changing output power Note This Setting is NOT required by Rule21 Standards This function...

Страница 29: ...king modes V Q V P indicates Volt Var First V P V Q indicates Volt Watt First 55 54 Figure 6 34 Power Rate Limit Power Rate 016 RateP_Sts US STOP Over frequency load shedding Fstart range 60 62Hz defa...

Страница 30: ...ected to an Area EPS 6 7 8 7 Voltage PCC Set This function is for maintenance personnel only wrong operation will prevent the inverter from reaching maximum power 57 56 6 7 8 8 Freq Watt This setting...

Страница 31: ...vent the inverter from reaching maximum power 59 58 6 7 13 Debug Parameter Figure 6 43 Debug Parameter as shown as below This section is applicable to maintenance personnel only Press the UP DOWN keys...

Страница 32: ...are included Power Parameter and Voltage Parameter YES ENT NO ESC Power para 1 000 6 Normal operation 6 Normal operation 61 60 6 7 16 I V Curve This function is used to scan the I V characteristic cu...

Страница 33: ...c Fault 63 62 Canadian Solar Three Phase Inverter does not require any regular maintenance However cleaning the dust on heat sink will help the inverter to dissipate the heat and increase its life tim...

Страница 34: ...lem e g the alarm message displayed on the screen and the status of the screen status indicator lights Other readings obtained from the Information sub menu refer to Section 6 4 will also be helpful 5...

Страница 35: ...is too low Inverter detects low DCV on internal bus Test Measure DC and AC voltages Compare with LCD Replace Inverter Internal damage Wire came loose during shipping 66 67 Inverter detects grid instab...

Страница 36: ...nnected wait for the night when the solar irradiance is low and the PV string current down below 0 5A Turn off the two DC switchs and fix the polarity issue If string polarity is correct please confir...

Страница 37: ...IEEE 1547 UL 1699B UL 1998 FCC UL 1741SA California Rule 21 RS485 Optional Wifi PLC Ethernet 70 71 Dimensions W H D Weight 1065 567 344 5 mm 41 9 22 3 13 5 inch 3 PE 480 Max DC input voltage Volts MPP...

Страница 38: ...1 Full load MPPT voltage range Volts 550 850 RS485 Optional Wifi PLC Ethernet 72 73 Dimensions W H D Weight 1065 567 344 5 mm 41 9 22 3 13 5 inch 3 PE 480 Max DC input voltage Volts MPPT voltage range...

Страница 39: ...1699B UL 1998 FCC UL 1741SA California Rule 21 RS485 Optional Wifi PLC Ethernet 74 75 Dimensions W H D Weight 1065 567 344 5 mm 41 9 22 3 13 5 inch 3 PE 480 Max DC input voltage Volts MPPT voltage ra...

Страница 40: ...Di at rated output power 3 Start up voltage Volts Max short circuit input current Amps Rated DC voltage Volts Rated grid frequency Hertz 180 1000 195 TYPE 4X 65dB A Intelligent redundant cooling 13120...

Страница 41: ...1000 P V curve for CSI 75K T480GL02 U Figure 10 2 CSI 75K T480GL02 U Inverter output power by input voltage P V curve for CSI 80K T480GL02 U Figure 10 3 CSI 80K T480GL02 U Inverter output power by inp...

Страница 42: ...1000 P V curve for CSI 90K T480GL03 U Figure 10 8 CSI 90K T480GL03 U Inverter output power by input voltage Figure 10 9 CSI 100K T480GL03 U Inverter output power by input voltage P V curve for CSI 75K...

Страница 43: ...LCD board for the Ethernet module RS485 from main COM board to the Ethernet module Ethernet Port Output RS485 Ports RJ45 Output RS485 Port Terminal Output RS485 Port Terminal Output Meter RS485 comin...

Страница 44: ...ompleted Record V AC in Notes 10 Grounding cable Good Poor INSTALLATION Check inverter condition after unpacking Install inverter mounting bracket according to installation instructions in user manual...

Страница 45: ...cable to the communication port 1 Switch the grid supply main Switch AC ON rst 2 Switch the DC switch ON If the voltages of PV arrays are higher than start up voltage the inverter will turn on The re...

Страница 46: ...eted Record address in Notes 7 Machine version For maintenance and reference please record the irmware revisions if applicable Completed Record with serial numbers 8 Operating parameter Record operati...

Страница 47: ...ting tilt Output power Input DC voltage Insulation limit K PV start up voltage Grid V Max V Min Frequency Max Min Reactive compensation PF Coniguration MPPT Individual MPPT Parallel Monitoring RS485 E...

Страница 48: ...to inverter site selection and installation 3 PHASE STRING INVERTERS KTL SERIES CSIF ST 016 A 0 INSTALLER S NAME INSTALLER S SIGNATURE COMPANY DATE Inverter serial numbers 1 2 3 4 5 6 7 8 9 10 11 12 1...

Отзывы: