CanadianSolar CSI-75K-T480GL03-U Скачать руководство пользователя страница 19

5. Commissioning

2.  Measure the voltage present between the positive and negative wires of each string. 

    If the open circuit voltage of the string is near the maximum value accepted by the inverter, 

    verify the string length.  Low ambient temperatures cause an increase in the string voltage 

    causing potential damage to the inverter.  

3.  Check the polarity of the string.  All digital meters have a negative (“-“) indicator that 

    indicates when a voltage is negative; in this case a string connected in reverse polarity.

WARNING

Input voltages higher than the maximum value accepted by the inverter 

(see “Specifications” in Section 9) may damage the inverter.

Although Canadian Solar inverters feature reverse polarity protection, 

prolonged connection in reverse polarity may damage these protection 

circuits and/or the inverter.

5.4.1.2 Leakage to ground

Measure leakage to ground to check for a DC ground fault.

5. Commissioning

5.4 Preliminary checks

WARNING 

High Voltage.

AC and DC measurements should be made only by qualified personnel.

5.4.1 DC configuration

5.4.1.1 VOC and Polarity

To measure the open circuit voltage (VOC) and polarity of the individual strings, perform 

the following steps:

5.4.1.1.1 Check string voltage

1.  Connect the positive lead of the meter to the positive string cable of the string under test. 

    Connect the negative lead of the meter to the negative string cable of the string under test. 

Verify DC configuration by noting the number of panels in a string and the string voltage. 

Measure VOC, and check string polarity. Ensure both are correct and VOC is in specification.

.35.

.34.

5.4.1.2.1 Detection of leakage to ground

Canadian Solar inverters are transformer-less  and do not have an array connection to ground.  

Any measurement of a fixed voltage between ground and either the positive or negative string 

wiring indicates a leakage (ground fault) to ground and must be corrected prior to energizing 

the inverter or damage to the inverter may result.

To measure leakage to ground, perform the following steps:

1.  Ensure that neither negative nor positive DC conductors are connected to the ground strip. 

2.  Measure each string positive connection to ground.

3.  Measure each string negative connection to ground.

4.  Verify the voltage is “floating”, not a consistent voltage to ground.  Make sure you notice the 

    units of the measurement.  mV is not the same as V. 

Measure VAC and verify voltage is within local grid standards.

       1).  Measure each phase to ground (L-G).

       

5.4.2.1 Measure VAC and frequency

       2).  Measure phases to the other phases in pairs (L-L).  PH A to PH B, PH B to PH C and 

             PH C to PH A.

       3).  If the meter is equipped, measure the frequency of each phase to ground.

       4).  Ensure each measurement is within local grid standards and the inverter specifications 

             as noted in Section 9 “Specifications”.

A phase rotation test is recommended to ensure the phases have been connected in the 

appropriate order. Canadian Solar inverters do not require a

specific phase rotation connection.  

However, the local utility may require a specific phase rotation or a record of the phase 

configuration of the installation.

5.4.2.2 Phase rotation test

Verify AC configuration.

5.4.2 AC configuration

Verify DC connections.

Lightly tug on each DC cable to ensure it is properly connected to the inverter.

5.4.3 DC Connections

Verify AC connections.

1.  Lightly tug on each AC cable to ensure it is fully captured in the terminal.

2.  Visually check for any stray strands that may not be inserted in the terminal.

3.  Check to ensure the terminal screws are the correct torque.

5.4.4 AC Connections

Содержание CSI-75K-T480GL03-U

Страница 1: ...com Customer Support Email service ca csisolar com This manual is subject to change without prior noti cation Copyright is reserved Duplication of any part of this issue is prohibited without written...

Страница 2: ...equipment has supplied The customer is fully liable for any modifications made to the system therefore any hardware or software modification manipulation or alteration not expressly approved by the ma...

Страница 3: ...ck mounting 3 4 Electrical Connections 17 18 3 4 1 Grounding 20 3 4 2 Connect PV side of inverter 22 3 4 3 Connect grid side of inverter 26 4 Communication Monitoring 6 5 1 Set Time 39 6 5 2 Set Addre...

Страница 4: ...ser manual 16 for 75K 18 for 80K 20 for 90 100 K 4 4 4 1 1 2 3 4 6 5 4 Hexagon bolt M10 40 LED lights LCD display 4 buttons Figure 1 2 Bottom view DC Switch AC output DC input AC Switch Vent COM COM M...

Страница 5: ...kaging regularly If packing is damaged wet pest damages etc repackage the inverter immediately Store inverters on a flat hard surface not inclined or upside down After 100 days of storage the inverter...

Страница 6: ...tilation must be present if the inverter is to be installed in a confined space Figure 3 1 Distances required between inverters NOTE Nothing should be stored on or placed against the inverter 3 Instal...

Страница 7: ...quite high 3 2 Product handling Figure 3 3 Handles used to move the inverter shown circled in red 3 1 2 5 Air circulation Do not install in small closed rooms where air cannot freely circulate To prev...

Страница 8: ...ical connections downward The steps to mount the inverter are listed below 1 Refer to Figure 3 6 drill holes for mounting screws based on the hole diameter of bracket using a precision drill keeping t...

Страница 9: ...install the inverter vertically If the inverter cannot be mounted vertically it may be mounted at angles greater than 15 degrees off horizontal Inverter cannot be mounted flat Vertical 15 Backward Fi...

Страница 10: ...the inverter are described below in table 3 1 All electrical connections must be in accordance with local or national standard Table 3 1 Electrical connections Parts Connection Cable size Torque DC te...

Страница 11: ...grounding terminal on the heatsink described below 1 It is recommended to use copper wire for the chassis ground Either solid conductor or stranded wire is acceptable Refer to local code standard for...

Страница 12: ...n see figure 3 23 Figure 3 18 Disassemble the Connector Cap nut Figure 3 19 Insert the Wire into the Connector Cap nut and contact pin Crimping plier Figure 3 22 Multimeter measurement Figure 3 23 Con...

Страница 13: ...he inverter Confirm proper string length and voltage range before connecting DC cable to the inverter NOTE The AC output neutral is not bounded to the ground The neutral wire is not necessary for the...

Страница 14: ...on box cover Figure 3 27 2 Strip the insulation of the wire past the cable crimping area of the OT terminal then use a hydraulic crimp tool to crimp the terminal The crimped portion of the terminal mu...

Страница 15: ...al 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 R S 4 8 5 A R S 4 8 5 B Use the network wire stripper to strip the insulation layer off the communication cable Using the standard wire sequence referenced in TIA EI...

Страница 16: ...e 4 8 System Work mode Network Manual Restart Reset Upgrade Device information Type SN Firmware version Current tiom Time zone Embedded Ethernet 1909583738 ME 121001 V1 0 6 20200612800 Fri Nov 06 2020...

Страница 17: ...by changing laptop to new IP address in range of inverter IP address and navigate to new inverter IP address System Work mode Network Manual Restart Reset Upgrade Obtain IP address automatically Save...

Страница 18: ...elect ENTER There are 4 sub menu options use the UP DOWN arrows to highlight ADVANCED SETTINGS Press enter to select 2 The screen will show that a password is required The default password is 0010 pre...

Страница 19: ...d do not have an array connection to ground Any measurement of a fixed voltage between ground and either the positive or negative string wiring indicates a leakage ground fault to ground and must be c...

Страница 20: ...w are followed in the exact order outlined 1 Select Grid Off in the Advanced Setting of Inverter LCD 2 Turn off the AC Switch between Canadian Solar inverter and Grid 3 Wait approximately 30 seconds d...

Страница 21: ...ode DRM NO Shows DRM Number I_DC01 Shows input 01 current value I_DC02 Shows input 02 current value I_DC20 Shows input 20 current value VPV_Total 1000 0V IPV_Total 99 0A V_A 345 7V I_ A 109 0A V_C 345...

Страница 22: ...move the cursor press up to select the number After enter the correct password the Main Menu will display a screen and be able to access to the following information 41 40 6 6 3 Version The screen sho...

Страница 23: ...e is fixed 6 6 7 Daily Records The screen shows history of changing settings Only for maintance personel 43 42 6 7 Advanced Settings Technicians Only NOTE To access to this area is for fully qualified...

Страница 24: ...166 V 244 2S V 166 0 16S 60 5Hz F 62Hz 2S F 2Hz 6 0 16S 57Hz F 59 5Hz 2S 57Hz F 0 16S 480V Rated L L 45 44 6 7 2 Grid ON OFF This function is used to start up or stop the power generation of Canadian...

Страница 25: ...DOWN key to move the cursor Press the UP key to revise the value Press the ENTER key to execute the setting Press the ESC key to return to the previous menu 6 7 7 Special Settings This function is app...

Страница 26: ...t 305V Figure 6 22 Volt VAR Voltage1 242V Voltage2 273V 1 NULL Description Inverter is not under any working mode 49 48 YES ENT NO ESC Power Factor 1 00 Figure 6 23 Fixed PF Figure 6 24 PF Range 4 Fix...

Страница 27: ...n working modes 1 NULL 2 Volt watt 3 Volt Var 4 Fixed PF 5 Reac power 6 Power PF 7 VgWatt UL 6 7 8 1 2 With Rule21 Standard selected NOTE The other three working mode P1 V Watt P1 V Var and P1 V P V Q...

Страница 28: ...ault value is PF 1 53 52 5 Reac power Not Required Description Inverter will generate reactive power based on changing output power Note This Setting is NOT required by Rule21 Standards This function...

Страница 29: ...king modes V Q V P indicates Volt Var First V P V Q indicates Volt Watt First 55 54 Figure 6 34 Power Rate Limit Power Rate 016 RateP_Sts US STOP Over frequency load shedding Fstart range 60 62Hz defa...

Страница 30: ...ected to an Area EPS 6 7 8 7 Voltage PCC Set This function is for maintenance personnel only wrong operation will prevent the inverter from reaching maximum power 57 56 6 7 8 8 Freq Watt This setting...

Страница 31: ...vent the inverter from reaching maximum power 59 58 6 7 13 Debug Parameter Figure 6 43 Debug Parameter as shown as below This section is applicable to maintenance personnel only Press the UP DOWN keys...

Страница 32: ...are included Power Parameter and Voltage Parameter YES ENT NO ESC Power para 1 000 6 Normal operation 6 Normal operation 61 60 6 7 16 I V Curve This function is used to scan the I V characteristic cu...

Страница 33: ...c Fault 63 62 Canadian Solar Three Phase Inverter does not require any regular maintenance However cleaning the dust on heat sink will help the inverter to dissipate the heat and increase its life tim...

Страница 34: ...lem e g the alarm message displayed on the screen and the status of the screen status indicator lights Other readings obtained from the Information sub menu refer to Section 6 4 will also be helpful 5...

Страница 35: ...is too low Inverter detects low DCV on internal bus Test Measure DC and AC voltages Compare with LCD Replace Inverter Internal damage Wire came loose during shipping 66 67 Inverter detects grid instab...

Страница 36: ...nnected wait for the night when the solar irradiance is low and the PV string current down below 0 5A Turn off the two DC switchs and fix the polarity issue If string polarity is correct please confir...

Страница 37: ...IEEE 1547 UL 1699B UL 1998 FCC UL 1741SA California Rule 21 RS485 Optional Wifi PLC Ethernet 70 71 Dimensions W H D Weight 1065 567 344 5 mm 41 9 22 3 13 5 inch 3 PE 480 Max DC input voltage Volts MPP...

Страница 38: ...1 Full load MPPT voltage range Volts 550 850 RS485 Optional Wifi PLC Ethernet 72 73 Dimensions W H D Weight 1065 567 344 5 mm 41 9 22 3 13 5 inch 3 PE 480 Max DC input voltage Volts MPPT voltage range...

Страница 39: ...1699B UL 1998 FCC UL 1741SA California Rule 21 RS485 Optional Wifi PLC Ethernet 74 75 Dimensions W H D Weight 1065 567 344 5 mm 41 9 22 3 13 5 inch 3 PE 480 Max DC input voltage Volts MPPT voltage ra...

Страница 40: ...Di at rated output power 3 Start up voltage Volts Max short circuit input current Amps Rated DC voltage Volts Rated grid frequency Hertz 180 1000 195 TYPE 4X 65dB A Intelligent redundant cooling 13120...

Страница 41: ...1000 P V curve for CSI 75K T480GL02 U Figure 10 2 CSI 75K T480GL02 U Inverter output power by input voltage P V curve for CSI 80K T480GL02 U Figure 10 3 CSI 80K T480GL02 U Inverter output power by inp...

Страница 42: ...1000 P V curve for CSI 90K T480GL03 U Figure 10 8 CSI 90K T480GL03 U Inverter output power by input voltage Figure 10 9 CSI 100K T480GL03 U Inverter output power by input voltage P V curve for CSI 75K...

Страница 43: ...LCD board for the Ethernet module RS485 from main COM board to the Ethernet module Ethernet Port Output RS485 Ports RJ45 Output RS485 Port Terminal Output RS485 Port Terminal Output Meter RS485 comin...

Страница 44: ...ompleted Record V AC in Notes 10 Grounding cable Good Poor INSTALLATION Check inverter condition after unpacking Install inverter mounting bracket according to installation instructions in user manual...

Страница 45: ...cable to the communication port 1 Switch the grid supply main Switch AC ON rst 2 Switch the DC switch ON If the voltages of PV arrays are higher than start up voltage the inverter will turn on The re...

Страница 46: ...eted Record address in Notes 7 Machine version For maintenance and reference please record the irmware revisions if applicable Completed Record with serial numbers 8 Operating parameter Record operati...

Страница 47: ...ting tilt Output power Input DC voltage Insulation limit K PV start up voltage Grid V Max V Min Frequency Max Min Reactive compensation PF Coniguration MPPT Individual MPPT Parallel Monitoring RS485 E...

Страница 48: ...to inverter site selection and installation 3 PHASE STRING INVERTERS KTL SERIES CSIF ST 016 A 0 INSTALLER S NAME INSTALLER S SIGNATURE COMPANY DATE Inverter serial numbers 1 2 3 4 5 6 7 8 9 10 11 12 1...

Отзывы: