![CanadianSolar CSI-75K-T480GL03-U Скачать руководство пользователя страница 30](http://html1.mh-extra.com/html/canadiansolar/csi-75k-t480gl03-u/csi-75k-t480gl03-u_installation-and-operation-manual_4093722030.webp)
6. Normal operation
6. Normal operation
6.7.8.4 10mins Voltage Set
This function is disabled and
not used for the US.
This function is for maintenance personnel only, wrong operation
will prevent the inverter from reaching maximum power.
6.7.8.5 Power Priority
Figure 6.36 Power Priority
This setting is used to set the priority between Active Power Control (Watt) and
Reactive Power Control (Var).
YES=<ENT> NO=<ESC>
Select: Var First
Two options are available: Watt First and Var First.
This function is for maintenance personnel only, wrong operation
will prevent the inverter from reaching maximum power.
6.7.8.6 Initial Settings
In initial settings it will reset each work mode from 6.5.8.1 to 6.5.8.4 back to default.
Figure 6.37 Initial Settings
Work
Mode
Default
Power
Rate
Default
Set the voltage at the PCC point.
This setting is required by RULE 21 requirements.
PCC: Point of Common Coupling, the point where a Local EPS is connected to an Area EPS.
6.7.8.7 Voltage PCC Set
This function is for maintenance personnel only, wrong operation
will prevent the inverter from reaching maximum power.
.57.
.56.
6.7.8.8 Freq-Watt
This setting is used to control real power based on the frequency excursion
This setting is applicable when Rule21 Standards are selected.
Start Freq: 60.50Hz
WGradient: 040%
Figure 6.38 Freq-Watt (1)
Start Freq: This is the frequency that active power reduction starts.
WGradient: This is the active power reduction rate in terms of the frequency.
Stop Freq: This is the frequency that stops the correction cycle.
Hysteresis: This indicates whether hysteresis is enabled.
f stop
f start
Reduced
Power
f
Wgradient
Hysteresis
Figure 6.39 Freq-Watt (2)
This function is for maintenance personnel only, wrong operation
will prevent the inverter from reaching maximum power.
6.7.9 Restore Settings
This section is applicable to maintenance personnel only.
→
Figure 6.40
Press the ENTER key to reset to factory defaults.
Press the ESC key to return to the previous menu.
Selecting “Restore Settings” displays the option shown below:
Are
you
sure
?
YES
=<
ENT
>
NO
=<
ESC
>