6. Operation

.31.

6. Operation

.30.

6.5.2 Grid ON/OFF

This function is used to start up or stop the power generation of Canadian Solar Single 

Phase Inverter (see Figure 6.18).

      Grid ON

        Grid OFF

Figure 6.18 Set Grid ON/OFF

Screens can be scrolled manually by pressing the UP/DOWN keys. Press the ENTER key 

to save the setting. Press the ESC key to return to the previous menu. 

This function is used to set the new password for menu “Advanced info.” and “Advanced 

information” (see Figure 6.19).

Enter the right password before set new password. Press the DOWN key to move the 

cursor, Press the UP key to revise the value. Press the ENTER key to execute the setting. 

Press the ESC key to return to the previous menu. 

6.5.4 Reset Password

Figure 6.19 Reset password

YES=<ENT> NO=<ESC>

Password: 0000

6.5.3 Clear Energy

Clear Energy can reset the history yield of inverter

These two functions are applicable by maintenance personnel only, wrong 

operation will prevent the inverter from working properly.

NOTE: 

This function is for technicians use only.

Press the UP/DOWN keys to select the standard (AS4777-02,AS4777-15, VDE4105, VDE0126, 

UL-240V-A, UL-208V-A, UL-240V, UL-208V, MEX-CFE, G83/2 (for 1-3.6kW models), G59/3 

(for 4-5kW models), EN50438 DK, EN50438 IE, EN50438 NL and “User-Def” function). 

Press the ENTER key to confirm the setting. Press the ESC key to cancel changes and returns 

to previous menu.

Selecting the “User-Def” menu will access to the following submenu (see Figure 6.17), 

Figure 6.17

Below is the setting range for “User-Def”. Using this function, the limits can be changed 

manually.

NOTE:

The " User-Def" function can be only used by the service engineer and 
must be allowed by the local energy supplier.

             OV-G-V1: 240---270V                                OV-G-F1: 50.2-53Hz(60.2-64Hz)

             OV-G-V1-T: 0.1---9S                                  OV-G-F1-T: 0.1---9S

             OV-G-V2: 240---300V                                OV-G-F2: 50.2-53Hz(60.2-64Hz)

             OV-G-V2-T: 0.1---1S                                  OV-G-F2-T: 0.1---9S

             UN-G-V1: 170---210V                                UN-G-F1: 47-49.5Hz(56-59.8Hz)

             UN-G-V1-T: 0.1---9S                                  UN-G-F1-T: 0.1---9S

             UN-G-V2: 110---210V                                UN-G-F2: 47-49Hz(56-59.8Hz)

             UN-G-V2-T: 0.1---1S                                  UN-G-F2-T: 0.1---9S

       OV-G-V1: 260V

      OV-G-V1-T: 1S

Press the UP/DOWN keys to scroll through items. Press the ENTER key to edit the 

highlighted item. Press the UP/DOWN keys again to change the setting. Press the ENTER 

key to save the setting. Press the ESC key to cancel changes and returns to the previous menu.

This function is used to select the grid's reference standard (see Figure 6.16).

YES=<ENT> NO=<ESC>

Standard:AS4777-02

Figure 6.16

6.5.1 Selecting Standard

             Startup-T

:

10-600S                                  

 

Restore-T:  10-600S 

NOTE:

This inverter inclding two level protections for voltage and frequency 
under user-def mode; please set the same value both level one and 
level two if the gird only have one level requriement, eg. Brazil...etc.

Содержание CSI-700TL1P-GI-FL

Страница 1: ...AN SOLAR USA INC North America Headquarters 3000 Oak Road Ste 400 Walnut Creek CA 94596 Tel 1 888 998 7739 Sales Inquiries Email sales us canadiansolar com Technical Inquiries Email service ca canadia...

Страница 2: ...6 Operation 24 5 Start Stop 5 1 Start the Inverter 5 2 Stop the Inverter 23 23 23 1 1 Product Description 3 1 2 Packaging 4 4 3 1 Connect PV side of inverter 13 4 3 2 Connect grid side of inverter 16...

Страница 3: ...tions 38 38 41 32 6 5 11 Export Power Set 6 5 9 Restore Settings 6 5 10 HMI Update 6 4 8 Warning Message 29 37 6 5 12 Restart HMI 6 5 13 Debug Parameter 6 5 14 DSP Update 6 5 15 Power Parameter 37 37...

Страница 4: ...important safety instructions which if not correctly followed could result in some damage or the destruction of the inverter 2 1 Safety Symbols Safety symbols used in this manual which highlight pote...

Страница 5: ...e solar panel s DC isolator shall be switched off 6 CAUTION The PV array Solar panels supplies a DC voltage when they are exposed to sunlight CAUTION Risk of electric shock from energy stored in capac...

Страница 6: ...ations 8 Figure 4 1 Recommended Installation locations To select a location for the inverter the following criteria should be considered Do not install in small closed spaces where air can not circula...

Страница 7: ...nverters are installed in one location a minimum 12inchs clearance should be kept between each inverter or other object The bottom of the inverter should be 20inchs clearance to the ground Visibility...

Страница 8: ...the inverter Figure 4 6 DC Connector Figure 4 7 DC Connector WARNING The inverter must be mounted vertically 4 Lift up the inverter be careful to avoid body strain and align the back bracket on the in...

Страница 9: ...nnector cap nut and contact pin Figure 4 8 Disassemble the Connector Cap nut Figure 4 9 Insert the Wire into the Connector Cap nut and contact pin iii Crimp the contact pin to the wire using a proper...

Страница 10: ...to assemble the AC grid terminal connectors are listed as follows a Disassemble the AC connector Strip the AC wires about 6mm Figure 4 15 Stripped AC Wires c Tighten up the cap on the terminal see Fig...

Страница 11: ...t GPRS monitoring Wi Fi monitoring Smart phone monitoring PC monitoring Web server Router Wi Fi monitoring Wi Fi box To protect the inverter s AC grid connection conductors Canadian Solar recommends i...

Страница 12: ...consumers mains and the solar supply 2 More than one RCD may be used Each RCD can protect one or more circuits Refer to figure 4 21 which is a simple guidance for installing a solar system with PV in...

Страница 13: ...Inverter power limited by over grid voltage LimByVar Inverter power limited by generating reactive power When inverter working normally there would be 5 status Logic interface is required by G98 and G...

Страница 14: ...Current of EPM 10 sec Work Mode The work mode of inverter DRM Number Show the number 01 08 Work Mode NULL DRM Number 08 10 sec Meter EnergyP The active power Meter EnergyP 0000000 00kWh 6 1 Main Menu...

Страница 15: ...password the Main Menu will display a screen and be able to access to the following information 1 Alarm Message 2 Running Message 3 Version 4 Daily Energy 5 Monthly Energy 6 Yearly Energy 7 Daily Reco...

Страница 16: ...reen shows the internal data of the Inverter see Figure 6 14 which is for service technicians only 01 05 01 25 E4 9D AA 06 10 C2 B5 E4 9D 55 Figure 6 14 Communication Data Press DOWN key to move the c...

Страница 17: ...d User Def function Press the ENTER key to confirm the setting Press the ESC key to cancel changes and returns to previous menu Selecting the User Def menu will access to the following submenu see Fig...

Страница 18: ...set 4 10mins OV G V set 5 Initial Settings This function is applicable by maintenance personnel only wrong operation will prevent the inverter from working properly 6 5 8 1 Enable logic interface set...

Страница 19: ...This function is used to shut down the Export Power Set 6 5 11 1 1 OFF 6 5 11 1 4 1 CT Sampling Ratio This function is used for change CT Sampling Ratio if customer select different CT The default ra...

Страница 20: ...t setting is ON 6 5 12 Restart HMI 6 5 13 Debug Parameter This function is used for manufacturer maintenance personnel only The function is used for restart the HMI This function is applicable by main...

Страница 21: ...otection limit if it s allowed by electrical company 1 Check connections and grid switch 2 Check the grid voltage inside inverter terminal 1 Reduce the module number in series 1 Restart inverter 2 Cha...

Страница 22: ...Leak PRO 01 02 03 04 Leakage current protection RelayChk FAIL Relay check fail 41 40 8 Trouble Shooting 47 52 or 57 62 Max DC input voltage Volts Rated DC voltage Volts MPPT voltage range Volts Max in...

Страница 23: ...rtz 8 5kg 50 500 3 47 52 or 57 62 Max DC input voltage Volts MPPT voltage range Volts Max input current Amps MPPT number Max input strings number Rated grid voltage Volts Rated output current Amps Pow...

Страница 24: ...frequency Hertz 3 47 52 or 57 62 Max DC input voltage Volts MPPT voltage range Volts Max input current Amps MPPT number Max input strings number Rated grid voltage Volts Rated output current Amps Powe...

Страница 25: ...rating surroundings humidity 310W 373H 160D mm 600 11 17 2 1 1 220 230 0 8leading 0 8lagging 50 60 97 5 96 8 99 5 8 8kg Transformerless IP65 20 dBA Natural convection 4000m 20 years 25 60 Display Moni...

Страница 26: ...and are properly ventilated Completed 5 Serial number Record the product serial numbers located on the side label Serial Numbers attached list 6 Solar modules Confirm PV module installation completion...

Страница 27: ...es CSI xx KTL GI 1 Switch the grid supply main Switch AC ON first 2 Switch the DC switch ON If the voltages of PV arrays are higher than start up voltage the inverter will turn on The red LED power wi...

Страница 28: ...using the front panel interface Completed Record current date time in Notes 6 Communication setting if avail Set communication with a unique address for each inverter Completed Record address in Notes...

Страница 29: ...t Output power Input DC voltage Insulation limit K PV start up voltage Grid V Max V Min Frequency Max Min Reactive compensation PF Configuration MPPT Individual MPPT Parallel Monitoring RS485 Ethernet...

Страница 30: ...ter site selection and installation 3 PHASE STRING INVERTERS KTL SERIES CSIF ST 016 A 0 INSTALLER S NAME INSTALLER S SIGNATURE COMPANY DATE Inverter serial numbers 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15...

Отзывы: