background image

 

1

 

INTRODUCTION 

 

Camus Hydronics proudly introduces its MicoFlame series 2 of commercial water heaters / 
hydronic boilers. These gas-burning appliances are thoughtfully designed for easy operation 
and maintenance. We are confident that you will come to appreciate the benefits of our product. 

1.     GENERAL INSTRUCTIONS 

 

The installation of this heater must conform to the requirements of the authority having 
jurisdiction or, in the absence of such requirements, to the National Fuel Gas Code, ANSI 
Z223.1 or CAN/CGA B149 Installation Codes. All electrical wiring must be done in accordance 
with the requirements of the authority having jurisdiction or, in the absence of such 
requirements, with the National Electrical Code, ANSI/NFPA 70 or the Canadian Electrical Code 
Part I , CSA C22.1 Electrical Code . 
 
Vent installations must be in accordance with Part 7, Venting of Equipment, of the National Fuel 
Gas Code, ANSI Z223.1, or Section 7, Venting Systems and Air Supply for Appliances, of the 
CAN. CGA B149, Installation Codes and applicable provisions of the local building codes. 
 
When required by the authority having jurisdiction, the installation must conform to the Standard 
for Controls and Safety Devices for Automatically Fired Boilers, ANSI/ASME CSD-1. 
 
The qualified installer shall instruct the end user in the safe and correct operation of this 
appliance and shall ensure that the heater is in safe working order prior to leaving the job site.

 

 

WARRANTY: 
 
Factory warranty shall apply only when the boiler is installed in accordance with 
local plumbing and building codes, ordinances and regulations, the printed 
instructions provided with it and good industry practices. 
 
Excessive water hardness causing a lime build-up in the copper coils or tubes is 
not a fault of the boiler and is not covered by warranty. Consult the factory for 
recommendations for use in hard water areas. 
 
Using or storing corrosive chemicals in the vicinity of this boiler can rapidly 
attack the copper tubes and coils and voids warranty. 
 
The primary heat exchanger of this boiler is intended to operate under non-
condensing conditions. Inlet temperatures must be maintained at 110 

°

F or 

higher. Warranty is void if the primary heat exchanger is allowed to operate in 
condensing mode. 
  
 Damage caused by freezing or dry firing voids warranty. 
 
 This boiler is not to be used for temporary heating of buildings under 
construction. 
 

Содержание MICOFLAME 2 Series

Страница 1: ...r appliance WHAT TO DO IF YOU SMELL GAS o Do not try to light any appliance o Do not touch any electrical switch do not use any phone in your building o Immediately call your gas supplier from a neigh...

Страница 2: ...8 RELIEF VALVE 10 9 FREEZE PROTECTION 10 10 WARNING REGARDING CHILLED WATER SYSTEMS 11 11 PIPING OF SYSTEM TO BOILER FIG 4 11 12 PLACING BOILER IN OPERATION 13 13 IGNITION SYSTEM SAFETY SHUT OFF DEVI...

Страница 3: ...ty having jurisdiction the installation must conform to the Standard for Controls and Safety Devices for Automatically Fired Boilers ANSI ASME CSD 1 The qualified installer shall instruct the end user...

Страница 4: ...installed above the level of the building s radiation system a low water cutoff device must be installed in the boiler outlet at the time of installation Some local codes require the installation of a...

Страница 5: ...tion leading to reversal of the natural draft action of the venting system Under these circumstances an engineered air supply is necessary If the heater is to be installed near a corrosive or potentia...

Страница 6: ...fans must be running in order for the appliance to proceed to trial for ignition MicoFlame series 2 is supplied with more than one burner may use burners that are not of identical size in order to acc...

Страница 7: ...to operate at inlet gas pressures not exceeding PSI 14 W C If higher pressures are present consult the gas company for correction When pressure testing the gas supply piping at pressures above PSI th...

Страница 8: ...upported approximately every 4 feet to prevent sagging and maintain a minimum upward slope of per foot from the boiler to the vent terminal When an existing boiler is removed from a common venting sys...

Страница 9: ...structions from the chimney and flue which might impede draft action Replace any damaged or deteriorated parts of the venting system A qualified service technician should follow this procedure when in...

Страница 10: ...efficient and is considered to be a category II or IV appliance Three venting options are available for this boiler in both condensing and non condensing configurations See Figure 2 for details Pleas...

Страница 11: ...ACNA AFTS 100 73 Standard When venting through unheated spaces with single wall vent insulation should be wrapped around the vent pipe to prevent flue gas condensation inside the vent Periodically che...

Страница 12: ...inst damage that could be caused by malfunctioning controls or excessive water pressure If a relief valve is not used warranty is void The relief valve is to be located as near as practical to the out...

Страница 13: ...tic means to prevent gravity circulation of chilled water through the boiler Chilled water in the boiler will create condensate on the boiler tubes which will collect in the combustion chamber causing...

Страница 14: ...radiation level it must be provided with a low water cutoff device at the time of boiler installation Available from factory A pressure relief valve is supplied with each MicoFlame series 2 boiler Th...

Страница 15: ...ance filled with air Start up boiler following instructions provided Operate entire system including pumps and radiation for at least 1 hour Check water level in expansion tank If level exceeds of tan...

Страница 16: ...he inlet temperature is greater than 110 F but not greater than 140 F no further adjustment is required e Check the inlet temperature after 5 minutes and make final adjustments 15 INSTANTANEOUS WATER...

Страница 17: ...t burner every six months for proper flame characteristics 16 1 MAIN BURNER The main burner figure 7 should display the following characteristics Acceptable CO and CO2 levels for complete combustion L...

Страница 18: ...1 6 1 9 1 6 1 9 1 2 1 6 1 2 1 6 2000 1 9 2 2 1 9 2 2 1 5 1 9 1 5 1 9 Depending on field conditions air box pressures will have to be adjusted accordingly Always set the appliance for a CO2 level in th...

Страница 19: ...e electrode does not appear overheated or fouled with carbon It may be necessary to clean the ignition electrode using steel wool Once the pilot appears to be properly set reinstall it into the applia...

Страница 20: ...ction 15 of this manual After the first season of operation inspect the heat exchanger and venting Follow the detailed instructions in section 6 of this manual CAUTION Label all wires prior to disconn...

Страница 21: ...If pilot fails to light and you suspect air in the line close the main manual valve and repeat lighting steps 1 thru 5 7 Once the pilot lights it should envelope the ignition rod and ground electrode...

Страница 22: ...und electrodes are positioned properly Clean with steel wool if necessary Verify that back of burner box is fully engaged into the retaining slot in the combustion chamber base 5 Pilot lights but main...

Страница 23: ...ICAL DIAGRAMS Each MicoFlame series 2 boiler will be provided with its own wiring diagram to guarantee that any options ordered with the unit are properly detailed The following diagram 99 5072 and 99...

Страница 24: ...22...

Страница 25: ...23...

Страница 26: ...24 22 EXPLODED VIEW...

Страница 27: ...25 23 MICO FLAME REPLACEMENT PARTS LIST...

Страница 28: ...standard warranty 2 Years six through ten replacement purchase price pro rated at the following schedule Year six 60 Year seven 65 Year eight 70 Year nine 75 Year ten 80 of the current list price of t...

Страница 29: ...t water heaters and heating boilers as well as a into every single unit For more information supplier of specialty HVAC products Our service line is open 24 hours 7 days a week on our innovative produ...

Отзывы: