1
INTRODUCTION
Camus Hydronics proudly introduces its MicoFlame series 2 of commercial water heaters /
hydronic boilers. These gas-burning appliances are thoughtfully designed for easy operation
and maintenance. We are confident that you will come to appreciate the benefits of our product.
1. GENERAL INSTRUCTIONS
The installation of this heater must conform to the requirements of the authority having
jurisdiction or, in the absence of such requirements, to the National Fuel Gas Code, ANSI
Z223.1 or CAN/CGA B149 Installation Codes. All electrical wiring must be done in accordance
with the requirements of the authority having jurisdiction or, in the absence of such
requirements, with the National Electrical Code, ANSI/NFPA 70 or the Canadian Electrical Code
Part I , CSA C22.1 Electrical Code .
Vent installations must be in accordance with Part 7, Venting of Equipment, of the National Fuel
Gas Code, ANSI Z223.1, or Section 7, Venting Systems and Air Supply for Appliances, of the
CAN. CGA B149, Installation Codes and applicable provisions of the local building codes.
When required by the authority having jurisdiction, the installation must conform to the Standard
for Controls and Safety Devices for Automatically Fired Boilers, ANSI/ASME CSD-1.
The qualified installer shall instruct the end user in the safe and correct operation of this
appliance and shall ensure that the heater is in safe working order prior to leaving the job site.
WARRANTY:
Factory warranty shall apply only when the boiler is installed in accordance with
local plumbing and building codes, ordinances and regulations, the printed
instructions provided with it and good industry practices.
Excessive water hardness causing a lime build-up in the copper coils or tubes is
not a fault of the boiler and is not covered by warranty. Consult the factory for
recommendations for use in hard water areas.
Using or storing corrosive chemicals in the vicinity of this boiler can rapidly
attack the copper tubes and coils and voids warranty.
The primary heat exchanger of this boiler is intended to operate under non-
condensing conditions. Inlet temperatures must be maintained at 110
°
F or
higher. Warranty is void if the primary heat exchanger is allowed to operate in
condensing mode.
Damage caused by freezing or dry firing voids warranty.
This boiler is not to be used for temporary heating of buildings under
construction.