14
Figure 5
•
Adjustment
procedure.
a. Fully open bypass and outlet valves.
b. With boiler running, read inlet temperature after 15 minutes.
c. If the inlet temperature is less than 110
°
F slowly close outlet valve until the inlet
temperature climbs to 110
°
F
d. If the inlet temperature is greater than 110
°
F but not greater than 140
°
F no
further adjustment is required.
e. Check the inlet temperature after 5 minutes and make final adjustments.
15. INSTANTANEOUS WATER HEATER
An instantaneous water heater is designed to deliver hot water without the use of a storage
tank. It is suitable for applications with variable load such as restaurants, condominiums,
apartments and motels. (See figure 6) Call factory for recommendations.