8. While the boiler is operating, check for flue gas leaks and proper vent operation. Seal
any flue gas leaks using appropriate gasket or sealing material. Carefully examine the
flue collector access panel and heat exchanger ends.
The MicoFlame series 2 is category 1, 85% efficient when supplied as a non-condensing
appliance. When supplied with the optional condensing cartridge, the MicoFlame series 2 is
95% efficient and is considered to be a category II or IV appliance. Three venting options are
available for this boiler in both condensing and non-condensing configurations. See Figure 2 for
details. (Please refer to Table 1 for vent dimensions)
Figure 2
7.1 OUTDOOR VENTING
When fitted with the factory supplied rain shield and UL approved vent cap, the MicoFlame
series 2 is self-venting. The following applies to outdoor installations:
1. Use only factory supplied rain shields.
2. Periodically check to ensure that air intake and vent cap are not obstructed.
3. Locate boiler at least 3 feet away from any overhang.