32
4-20mA/ 0-10Vdc Setpoint Operation (Standalone, Lead Lag)
Description
Electrical Connection(s)
Programming Instructions
•
Boiler operates with variable
setpoint determined by 4-
20mA incoming signal
•
Modulates on boiler inlet
sensor (default)
•
Heat demand is generated
when Remote Operator is
closed and 4-20mA or 0-
10Vdc signal is present.
1)
Press
and
2)
Press
[CH – Central Heat Configuration]
3)
Press the to arrive at
Setpoint
4)
Select
Setpoint Source = S2 (J8-6) 4-20mA
5)
Select
4mA water temperature
6)
Select
20mA water temperature
7)
Place toggle switch to
REMOTE
for remote operation (if required)