28
4.7
INSTANTANEOUS WATER HEATER
An instantaneous water heater is designed to deliver hot water without the use of a storage tank. It is suitable for applications with variable
load such as restaurants, condominiums, apartments and motels and typically used in conjunction with tempering valves to achieve
temperature control. In some applications it may be appropriate to provide a flow through tank to act as a buffer. Consult factory for
recommendations. (See Figure 19)
Figure 19: Typical Instantaneous Water Heating System
Table 8: Flow and Pressure Drop (Ft.) at a Given Temperature Rise (AV500-4000)
Model
Absolute
Minimum Flow
(10°F
∆T at
1/23rd input)
Pressure
Drop
∆P
Flow at
20°F
∆T
(Maximum
Input)
Pressure
Drop
∆P
Flow at
40°F
∆T
(Maximum
Input)
Pressure
Drop
∆P
Flow at
60°F
(Maximum
Input)
Pressure
Drop ∆P
500
n/a
n/a
47.2
1.8
23.6
0.5
15.7
0.2
600
n/a
n/a
56.6
2.6
28.3
0.6
18.9
0.3
800
6.6
0.03
74.8
4.5
37.4
1.1
24.9
0.5
1000
8.2
0.05
93.4
7.0
46.7
1.8
31.2
0.8
1200
9.9
0.02
112.2
2.0
56.1
0.5
37.4
0.2
1400
11.5
0.02
130.8
2.7
65.4
0.7
43.6
0.3
1600
13.2
0.03
149.6
3.9
74.8
0.8
49.9
0.4
1800
14.8
0.04
168.2
4.4
84.1
1.2
56.1
0.5
2000
16.5
0.05
189.8
5.6
94.9
1.4
63.2
0.6
2500
20.6
0.07
237.2
8.8
118.6
2.2
79.1
1.0
3000
24.7
0.01
284.6
1.6
142.3
0.4
95.0
0.2
3500
28.9
0.02
332.0
2.2
166.0
0.6
110.7
0.3
4000
33.0
0.02
379.4
2.9
189.7
0.7
126.5
0.3
4.8
WATER HEATER THERMOSTAT SETTING
1. This appliance is provided with an electronic temperature controller as detailed in Section 6.
2. The maximum setting for this water heater is 140°F.
3. There is a hot water scald potential if the temperature controller is set too high.
4.9
WATER FLOW SWITCH (shipped loose)
A water
Flow Switch
is to be installed in the outlet piping on all heating boilers and hot water supply boilers. The
Flow Switch
is wired in
series with the 24VAC safety control circuit.
Содержание ADVANTUS AVH 500
Страница 2: ......
Страница 3: ......
Страница 38: ...31 Figure 23 Recommended Piping with Reverse Return and Variable Primary Flow...
Страница 70: ...63 Figure 44 Typical Gas Train Models AV1000 3000 Figure 45 Typical Gas Train Models AV3500 4000...
Страница 88: ...81 PART 12 EXPLODED VIEW Figure A...
Страница 89: ...82 Figure B FAN BURNER ASSEMBLY AV500 600 some items may not be as shown...
Страница 90: ...83 Figure C FAN BURNER ASSEMBLY AV800 4000 some items may not be as shown...
Страница 91: ...84 Figure D Figure E...
Страница 92: ...85 Figure F Figure G...
Страница 93: ...86 Figure H CONTROL BOARD ASSEMBLY...
Страница 100: ...93 PART 13 ELECTRICAL DIAGRAMS...
Страница 101: ...94...
Страница 102: ...95...