58
Model 800
Light off the boiler and adjust the
Low-End Valve
as described above for models 500
– 600.
After the low fire settings are stable, ramp the boiler firing rate to 100% using the boiler control and bring system temperatures up to
130
o
F or to highest system design temperatures to minimize or eliminate condensate.
Models 1000
– 4000
Light off the boiler and adjust the
Low-End Valve
as described above for models 500
– 600.
Once the interface relay has switched to the
High-End Valve
, while maintaining the lowest possible water temperature, observe the
differential gas pressure when running with the
High-End Valve
. The differential gas pressure must not drop
below a minimum of 0.25”
W.C. Once the boiler has run for at least 5 minutes with dead cold water, there should be a maximum amount of condensate in the heat
exchanger. At this point adjust the combustion for CO
2
.
The boiler must continue to run with stable combustion without making any howling noise which usually happens from an overly rich
mixture. Once settings are complete at low fire, continue to run the machine for at least 5 more minutes and record the final low fire input
and the combustion data.
To ensure the coldest possible water temperatures for set up on multiple boiler systems, the low fire combustion should be established
on all boilers before setting any boiler high fire combustion rates.
In order to perform adjustments to the gas valve, the
Advantus
must be firing before proceeding.
Figure 39: AV800
– 1400 Low End Gas Valve
Lift top cover to access high fire air/gas ratio
adjustment (use 3mm allen key for adjustment,
counter-clockwise increases CO
2
)
Low fire air/gas ratio adjustment (use T-40 for
adjustment, counter-clockwise increases CO
2
)
Gas
Inle
t
High fire air/gas ratio adjustment
(use slotted screwdriver for
adjustment, counter-clockwise
increases CO
2
)
Figure 40: AV 500
– 600, 1000 High End Gas Valve & 1600 – 4000 Low End Gas Valve
Low fire air/gas ratio adjustment
(use T-40 for adjustment,
clockwise increases CO
2
)
Содержание ADVANTUS AVH 1000
Страница 2: ......
Страница 3: ......
Страница 38: ...31 Figure 23 Recommended Piping with Reverse Return and Variable Primary Flow...
Страница 70: ...63 Figure 44 Typical Gas Train Models AV1000 3000 Figure 45 Typical Gas Train Models AV3500 4000...
Страница 88: ...81 PART 12 EXPLODED VIEW Figure A...
Страница 89: ...82 Figure B FAN BURNER ASSEMBLY AV500 600 some items may not be as shown...
Страница 90: ...83 Figure C FAN BURNER ASSEMBLY AV800 4000 some items may not be as shown...
Страница 91: ...84 Figure D Figure E...
Страница 92: ...85 Figure F Figure G...
Страница 93: ...86 Figure H CONTROL BOARD ASSEMBLY...
Страница 100: ...93 PART 13 ELECTRICAL DIAGRAMS...
Страница 101: ...94...
Страница 102: ...95...