35
5.7.1
SERVICE PARTS
The electronic ignition module is not repairable. Any modification or repairs will invalidate the warranty and may create hazardous
conditions that result in property damage, personal injury, fire, explosion and/or toxic gases. A faulty
Hot Surface Igniter
or ignition module
MUST BE replaced with a new factory approved unit only. A factory approved igniter, ignition control module and
UV Scanner
for this
specific unit is available from your local distributor. DO NOT use general purpose field replacement ignition modules, igniters or UV
Scanners. Each appliance has one ignition module, one
Hot Surface Igniter
and one
UV Scanner
.
5.7.2
IGNITION MODULE LOCKOUT FUNCTIONS
The ignition module may lockout in either a hard lockout condition requiring pushing of the reset button to recycle the control for a CSD-
1 requirement or a soft lockout condition which may be reset automatically once the error clears. A typical hard lockout fault can occur
with a single trial for ignition CSD-1 module. Pushing the reset button on the ignition control is the only way to reset an ignition module
that is in a hard lockout condition. The reset button is located on the ignition module. Turning the main power “OFF” and the “ON” or
cycling the thermostat will not reset a hard lockout condition. Wait until the display shows the temperatures on screen before pushing
the reset button when the ignition module is in a hard lockout.
5.8
Advantus CONTROLLER
Table 10: Connector Description
Connector
Connector Description
J1
UV Scanner, Ground
J2
Fan Modulation (AV500 & 600)
J3
Display, Lead Lag, Modbus Communication
J4
24VAC Power, Pump, VFD
J5
Gas Valve, Safety Interlock String
J6
Safety Annunciation, Remote Operator
J8
24 VAC Power, Inlet, Outlet Sensor
J9
DHW, Stack Sensor
5.9
ERROR TABLE
The following tables provide a description of all the possible errors with the
Advantus
appliance. Errors can be divided into two groups.
Alert errors (will disappear when error is gone) and lockout errors (can only be reset by the RESET button).
When the control is in error, the pump will be running. This is done to prevent the freezing of the central heating circuit when the boiler
is in error during the winter period. For some non-volatile lockouts, the pump will not be running. See table below for more details.
Table 11: Lockout Codes
#
Description
1
Unconfigured safety data
2
Waiting for safety data verification
3-46, 58-60, 97-99, 143-148, 172-178
Internal Fault. Replace SOLA Controller
47
Flame rod to ground leakage
48
Static Flame
Содержание ADVANTUS AVH 1000
Страница 2: ......
Страница 3: ......
Страница 38: ...31 Figure 23 Recommended Piping with Reverse Return and Variable Primary Flow...
Страница 70: ...63 Figure 44 Typical Gas Train Models AV1000 3000 Figure 45 Typical Gas Train Models AV3500 4000...
Страница 88: ...81 PART 12 EXPLODED VIEW Figure A...
Страница 89: ...82 Figure B FAN BURNER ASSEMBLY AV500 600 some items may not be as shown...
Страница 90: ...83 Figure C FAN BURNER ASSEMBLY AV800 4000 some items may not be as shown...
Страница 91: ...84 Figure D Figure E...
Страница 92: ...85 Figure F Figure G...
Страница 93: ...86 Figure H CONTROL BOARD ASSEMBLY...
Страница 100: ...93 PART 13 ELECTRICAL DIAGRAMS...
Страница 101: ...94...
Страница 102: ...95...