38
PART 6 CONTROL PANEL
6.1
APPLIANCE TEMPERATURE CONTROLLER
The appliance is provided with a control panel at the front. Operating controls are installed inside the control box and are accessible by
undoing the (2) slotted screws and swinging the door open. The diagnostic information center as well as the on/off switch and the
appliance temperature controls reside on the control box door. The ignition module, VFD, transformer and relays are mounted on the
internal panel.
Figure 30: Control Panel Front
The SOLA icons will appear in one of four colors indicating the boiler status:
Blue:
Normal operation
Red:
Lockout Condition
Yellow: Holding Mode
Grey:
Communication Error
The Boiler Temperature Controller for this appliance is the Honeywell SOLA. It initiates the local call for heat and sets the target return
(appliance inlet) water temperature. This controller offers a range of operation modes which provides set point as well as modulating
control. It provides the following:
Readings of inlet and outlet water temperatures as well as flame signal.
Operation as an auto reset limit
Operation as a control for inlet water temperature, outlet temperature, system temperature.
70°F
ΔT heat exchanger protection algorithm
Available storage tank mounted sensor used in conjunction with inlet sensor.
Adjustable: target temp, inter-stage differential, on delay between stages, minimum on time per stage, minimum off time per
stage.
Display of run hours for maintenance purposes. Counter wraps around at 10000 hours.
Flame failure signal
JST and Molex connectors for ease of service.
Error message display in text.
Manual override of boiler input rate for combustion.
Pump exercising feature runs pump 10 seconds every three days in the event of no pump operation.
Levels of access
Two levels of access to simplify the use of the boiler.
User
: Access to general boiler and display settings and adjustments to the central heating, domestic hot water, and lead lag setpoint.
Installer
: Access to all user parameters and allows for changes to additional boiler parameters to allow for ease of startup and
serviceability.
NOTE
Due to the sensitivity of the touchscreen controller, using a stylus is recommended for accuracy
Содержание ADVANTUS AVH 1000
Страница 2: ......
Страница 3: ......
Страница 38: ...31 Figure 23 Recommended Piping with Reverse Return and Variable Primary Flow...
Страница 70: ...63 Figure 44 Typical Gas Train Models AV1000 3000 Figure 45 Typical Gas Train Models AV3500 4000...
Страница 88: ...81 PART 12 EXPLODED VIEW Figure A...
Страница 89: ...82 Figure B FAN BURNER ASSEMBLY AV500 600 some items may not be as shown...
Страница 90: ...83 Figure C FAN BURNER ASSEMBLY AV800 4000 some items may not be as shown...
Страница 91: ...84 Figure D Figure E...
Страница 92: ...85 Figure F Figure G...
Страница 93: ...86 Figure H CONTROL BOARD ASSEMBLY...
Страница 100: ...93 PART 13 ELECTRICAL DIAGRAMS...
Страница 101: ...94...
Страница 102: ...95...