Testing the Igniter
5
1.
Inspect the ignition electrode for cracks.
2.
Inspect the ignition cable for cracks.
3.
Inspect the electrode gap, ensuring the gap is 1/8”.
•
With the gun still outside the burner casing, re-connect the
ignition cable to the igniter.
•
Ensure the gas gun is WELL GROUNDED to the burner
housing when testing for spark.
•
Reset the burner control and check for spark after the pre-
purge.
•
Keep a close eye on the electrode as the spark will only
appear for 1 second AFTER the 60 second pre-purge.
Ignition Cable
Electrode (Gap 1/8”)
✓
No spark indicates a defective igniter
SHUT OFF the gas supply to the burner before testing!