Using a Combustion Analyzer
43
•
Turn on the burner and let it run for 5 minutes.
•
Insert your combustion analyzer probe into the flue stack hole.
•
Adjust air settings on burner until you have an (Oxygen) reading between 3% to 4%.
•
Check to ensure that your CO (Carbon Monoxide) levels are no higher than 0-50 PPM.
•
Start up complete.
While the flue-stack is cold, pre-
drill a 1/4” hole in the flue
-
stack 18” above the
heater flue collar.