RF450 Spread Spectrum Radio
LEDs flash when
LoggerNet
command transmitted but no response from
datalogger:
1.
Check SC12 cable on the datalogger's CS I/O port.
2.
Check SDC address in RF450.
3.
Check SDC address in datalogger.
4.
Check the baud rate of
LoggerNet
; it should match the baud rate of the
RF450 attached to it.
Using the diagnostics port.
A special FreeWave Diagnostics cable and software (CSI part number 20625)
can be useful in troubleshooting radio problems. Contact FreeWave Inc. for
more information on using the Diagnostics cable.