NL200/201 Network Link Interface
16
The NL200/201 must be connected to the datalogger before
configuring the datalogger with
DevConfig
. If it is not connected,
the TCP/IP settings will not be displayed.
7.2.4
LoggerNet
Setup
The next step is to run
LoggerNet
and configure it to connect to the datalogger
via the Ethernet port. (See example in FIGURE
7-2
below.)
x
In the
LoggerNet Setup
screen, press
Add Root
and choose
IPPort
. Input
the datalogger’s IP address and port number. The IP address and port
number are input on the same line separated by a colon. (The datalogger’s
default port number is 6785. It can be changed using
DevConfig
. Unless
firewall issues exist, the port number does not need to be changed from its
default value.)
x
Add a PakBus® Port.
x
Add the datalogger (CR800, CR1000, or CR3000) and input the PakBus®
address of the datalogger.
x
You can verify that your settings are correct by selecting the datalogger in
the Network Map, selecting the Clock tab, and pressing
Check Clocks
. If
your settings are correct, you should see the current clock of your server
and datalogger.
FIGURE 7-2. Bridge mode LoggerNet setup
NOTE