Appendix B. Introduction to CRBasic Programming
B-10
true. When it is false,
DisableVar
is false. When
False
is entered as
the argument for
DisableVar
, all readings are included in the average.
The average of variable
Oscillator
does not include samples occurring
when
Flag1
is true, which results in an average of
2
; when
Flag1
is
false (all samples used), the average is
1.5
.
TABLE B-3. Data Types in Final-Data Memory
Name
Argument
Description
Word Size
(Bytes)
Notes
Resolution / Range
FP2
FP2
Campbell Scientific
floating point
2
Default final-memory data type. Use
FP2
for stored data requiring 3 or 4
significant digits. If more significant
digits are needed, use
IEEE4
or an
offset.
Zero
Minimum
Maximum
0.000
±0.001
±7999.
Absolute Value
Decimal Location
0 – 7.999
X.XXX
8 – 79.99
XX.XX
80 – 799.9
XXX.X
800 – 7999.
XXXX.
IEEE4
IEEE4
or
Float
IEEE floating point
4
IEEE Standard 754
±
1.4E–45 to
±
3.4E38
IEEE8
IEEE8
or
Double
Double precision
floating point
8
IEEE Standard 754
Use to minimize floating point errors
when doing floating point
calculations or to store measurements
of high-resolution digital sensors.
Suitable for storing numbers larger
than Longs.
±4.94065E-324 to ±1.79769E308
Long
Long
Signed integer
4
Use to store integer data.
Speed: integer math is faster than
floating point math.
Resolution: 32 bits.
Suitable for storing whole numbers,
counting numbers, and integers in
final-data memory. If storing non-
integers, the fractional portion of the
value is lost.
–2,147,483,648 to +2,147,483,647
UINT2
UINT2
Unsigned integer
2
Use to store integer data.
Use to store port or flag status.
When
Public
Float
s convert to
UINT2
at final data storage, values
outside the range 0 – 65,535 yield
unusable data.
INF
converts to
65,535.
NAN
converts to 0.
0 to 65,535
UINT4
UINT4
Unsigned integer
4
Use to store positive count data ≤
2,147,483,647.
Other uses include storage of long ID
numbers (such as those read from a
bar reader), serial numbers, or
address.
May also be required for use in some
Modbus devices.
0 to 4,294,967,295