![Camille Bauer SIRAX MT7000 Скачать руководство пользователя страница 27](http://html1.mh-extra.com/html/camille-bauer/sirax-mt7000/sirax-mt7000_operating-manual_3673833027.webp)
PM 1001939 000 00
AC/DC Current and Voltage Converter SIRAX MT7000/MT7050
27/32
40007
Flag Measurement
Bit 0: Ah saving
0=Ah disabled
1=Ah enabled
Bit 1...2: Measurement channel
0=Input 1A/5A
1=Input 20mA / 100 mA
2=Input 1V
3=Input 10V
Bit 3: RTD measurement
0=2 wire RTD
1=3 wire RTD
Bit 4: Output Type
0=Voltage 0...10 V
1=Current 0...20 mA
Bit 5...6: Output measurement retransmitted
0=I
RMS
1=I
AC
2=I
DC
3=Temperature
Bit 7: FFT representation
0=Absolute
1=Relative to the I1 value
Bit 8: THD calculation
0=Only AC components
1=Including DC components
Bit 9...10: Temperature sensor
0=PT100
1=NTC 10 kΩ
2=NTC 100 kΩ
3=NTC Steinhart-Hart
Bit 11...12: Mesurement Format
(Reg. 40148...40320)
0=Float (LSW First)
1=Float (MSW First)
2=Hundredth (Float *100) (LSW First)
3=Hundredth (Float *100 SW) (MSW First)
Bit 13: Integrator condition
0=Integrator disabled
1=Integrator enabled (Rogowski input)
Bit 14: Output switch initial condition
0=Closed initial condition
1=Open initial condition
Bit 15: Measurement filter
0=Filter disabled
1=Filter enabled
Unsigned short
R/W
16408
(Ah Disabled,
Input 1A/5A,
Rtd 3 W, Current
0..20mA,
I Rms Out, FFT
Representation
Absolute, Only
AC Components,
Pt100, Float
Type, Integrator
Disabled, Open
Init Cond, Filter
disabled)
40008
LED Settings
Set the yellow led (COMM LED) according to the
corresponding bit set:
0=Fail Eeprom
1=Input Underrange
2=Input Overrange
3=Output Underrange
4=Output Overrange
5=RTD Out of the range
6=RTD Third Wire error
Unsigned short
R/W
RTD
dritter Draht-
fehler
40009
Transducer Ratio
If Input 1A / 5A, 20 mA / 100 mA
→
Current
transformer ratio M/N (Example: TA ratio = 600: 5
→
transducer ratio = 120; TA ratio = 1000: 1
→
transducer ratio = 1000)
If Input 1V, 10V
→
1/Sensitivity [V/A] (Example: Sen-
sitivity = 100mV / 1KA
→
transducer ratio = 10000;
Sensitivity = 4V / 400A
→
transducer ratio = 100)
Float (LSW first)
R/W
1
40011
Minimum Current
Ripple
Minimum threshold under which the instrument reads
0 independent from the input value
Float (LSW first)
R/W
0
40013
DC Filter
Number of tenth seconds for I RMS value in DC
Unsigned short
R/W
10
40014
AC Filter
Number of zero crossings for I RMS value in AC
Unsigned short
R/W
50
40015
Sec. For Mean Rms
Register in seconds (0..30) for RMS averaget
Unsigned short
R/W
0