PM 1001939 000 00
AC/DC Current and Voltage Converter SIRAX MT7000/MT7050
26/32
Now select whether you want to save the configuration in a file or
transfer it to the device.
This screen allows you to save the configuration in to a file.
This screen allows you to check the functionality of the device. The
current values, harmonics and temperature values can be displayed.
7.2. Programming over Modbus Adress-Register
Modbus
Adress
Register Name
Comment
Register Type
Read /
Write
Default values
40001
Maschine_ID
Maschine ID
Unsigned short
R
15 or 25
40002
HW/FW_Version
Hardware (MSB) and Firmware (LSB) Version
Unsigned short
R
40003
Address
Modbus Address
Unsigned short
R/W
1
40004
Delay
Machine answer delay
Unsigned short
R/W
1
40005
Baudrate
Baudrate:
0=1200 / 1=2400 / 2=4800 / 3=9600 / 4=19200 /
5=38400 / 6=57600 / 7=115200
Unsigned short
R/W
3
40006
Parity
Not used (always none)
Unsigned short
R/W
0