![Camille Bauer 175267 Скачать руководство пользователя страница 29](http://html1.mh-extra.com/html/camille-bauer/175267/175267_manual_487930029.webp)
PM 1000288 000 00
Device handbook SIRAX BT5100
29/32
Auxiliary supply voltage:
Rated Value ±1%
Auxiliary supply frequency:
Rated Value ±1%
Output Load:
Rn = 7.5 V / Y2 ± 1% With DC current output signal.
Rn = Y2 / 1 mA ± 1% With DC Voltage output signal.
Additional Error:
Temperature infl uence:
± 0.2% /10 K
Safety
Protection Class:
II (Protection Isolated acc. to EN 61010-1, EN 61010-2-030)
Protection:
IP 40, housing acording to EN 60529
IP 20,terminal according to EN 60529
Pollution degree:
2
Overvoltage category:
III, 300V
Insulation test voltage:
50Hz,1min. (EN 61010-1)
3700V, Input versus all other circuits
3700V, Auxiliary supply versus outer surface and output
490V, Output versus output versus each other versus outer surface.
Installation Data:
Material:
Lexan 940 (polycarbonate),
V-0 acc. to UL94, self-extinguishing,
non-dripping, free of halogen
Mounting position:
Rail mounting / wall mounting
Weight: Approx.
0.4kg
Connection Terminal
Connection Element:
Conventional Screw type terminal with indirect wire pressure
Permissible cross section
of the connection lead:
≤ 4.0 mm single wire or 2 x 2.5 mm Fine wire
Environmental
Nominal range of use:
0 °C … 23 °C … 45 °C (usage Group II)
Storage temperature:
-40 °C to 70 °C
Relative humidity of annual mean:
≤ 75%
Altitude: 2000m
max
Ambient tests:
EN 60068-2-6:
Vibration
Acceleration:
± 2 g
Frequency range:
10 … 150 … 10Hz,
Rate of frequency sweep:
1 octave/minute
Number of cycles:
10, in each of the three axes
EN 60068-2-7:
Shock
Acceleration:
3 x 50g
3 shocks in each direction
EN 60068-2-1/-2/-3
Cold, Dry, Damp heat
EN 61000-4-2/-3/-4/-5/-6, EN 55011
Electromagnetic compatibility