EMC_SPEC040_CLCR.doc
Rev. E
–
2021 10 18
45/63
Install & Operating Manual
CleanSeal V3
Filter Installation / Exchange
CAUTION:
The media pack of a traditional HEPA filter panel is extremely sensitive.
This is no longer an issue for latest generation filters like Camfil EnerGuard
, but
generally speaking, filters have to be handled with the utmost care to avoid
creating damage during installation.
DO NOT place objects on or manipulate filter panels by touching the media,
even for panels with protective grid.
Handle filter panels by the frame only !
The features of the CleanSeal toolless filter clamping system support safe and easy filter change.
•
Before inserting the filter, make sure all clamping blocks are rotated parallel to the housing wall.
•
Insert the filter into the housing and push up, until the retainer springs lock with a distinct click.
The filter is now safely maintained, clamps may be operated with both hands free.
•
Rotate the clamps out over the filter and close clamping levers.
•
For filter deinstallation, proceed in reverse order. Push on retainer springs to release the filter.
PLEASE NOTE:
Clamping settings will be stable over time, unless clamping levers get rotated
inadvertently. Settings are adjustable,
see § 10.2
CAUTION:
In case of integrity issues at installation, check all possible root causes.
DO NOT overcompress filter gaskets, as damage might result.
NO
NO
NO