Install & Operating Manual
CleanSeal V3
Controlling Multiple Housings with IntegriBox
IntegriBox will allow remote aerosol injection and upstream pressure readings for up to 5 (10) housings.
•
Connect the “+” port of the manometer to the relevant upstream pressure port for a pressure drop
reading against the ambient room pressure.
PLEASE NOTE:
The box for technical areas features an additional pressure port for remote readout
of the downstream room pressure
•
Connect an aerosol generator to the injection port
using a D12 tube compatible with
quick-connect fittings. Push the locking ring on the fitting to release.
PLEASE NOTE:
Make sure the capacity of your generator is sufficient to compensate for the
particle loss, function of the injection tube length.
Upstream pressure port
Aerosol injection port
D12 mm