background image

if the automation system is closing;

if the automation system is opening. The system will then re-elose when
actuated by the aulomatic closing timer.

during opening

If the obstacle is still detected:

during closing

{\

STARTING

UP THE SYSTEM

VERIFICHE

PRELIMINARI

Before start-up, make sure that:

.{

The electric lock (if installed) has been manually released;

.{

The proper tension has been applied to the belt (see p. 12);

.{

The checks described on p. 13 {checking for proper assembly} have been performed;

.{

No objects are present along the path taken by the door wings as they move;

.{

All mounting hardware has been properly tightened;

.{

The sensors are correctly aligned and are not blocked;

.{

The desired functions have been correctly selected on the dip switches (see p. 16);

.{

The trimmers have been set to their midpoints {see p. 15},

START .UP/CALIBRATION

1,

Tum on the power to the unit

- LED no. 3 will light up

2.

Move dip switch 1 to ON

- LED no. 3 will turn off and LED no. 8 will light up
- The system will execute an closing and opening cycle at reduced speed and will stop at the maximum open
position (" at the end of the cycle
- LEOs no. 6-7-8 will light up

3.

Move dip swilch 1 10 OFF

- LEOs no. 6-7-8 will turn off and LED no. 3 will light up

4,

Make sure that function swilch MA7041 (if installed) has been set

10

the "open' position (with the LEOs lit in

sequence)

5.

Enter an "open" command on 2-R1/2-R2 or by pressing the open key (see p.15).
-the automation will position itself at the closing point

6.

Send an opening signal
-the automation will perform a complete manoeuvre

7.

Adjust the movement of the doors using the door trimmers (see p.15).

8.

Adjust trimmer 3 to obtain the desired delay before automatic closing

9.

Trimmer 2 can be adjusted only if function switch MA7041 has been installed and if this switch has been set
to the "partial opening" position

10. Use the lever on the manual release system to re-arm the electric lock (if installed)

0,

If the automation

system stops during the closing cycle, the motor polarity may be incorrect.

If this occurs, proceed

as

follows:

-Disconnect

the mains power

- Make sure dip switch

1 is

set to OFF

- Reverse connections

M-N on the terminal board for the motor, which is IDeated in the electrical

cabinet (on the right)

- Begin another start-up/calibration

procedure

starting from point 1.

SAFETY FUNCTIONS

- Actions

taken by the automation

system

when a safety device trips

When the safety sensor detects an obstacle, the microprocessor

control system in the electrical cabinet

actuates:

re-openlng,

a stop,

the automation will automatically

try 4 times to close the doors, and then it

will stop them in the open position, awaiting a new command

the automation system will stop with the door wings resting against the
obstacle and will re-c1ose when actuated by the automatic closing timer.

The system will attempt to open the door three times, and then pause with
the door wings resting against the obstacle until another command is given;

(In both cases, normal operation with the programmed

settings will automatically

resume when the

obstacle is removed)

Changing

the direction

of door opening

(Rodeo 1)

- With the door stopped, reverse connections M-N on the terminal board for the motor, which is located in the

electrical cabinet (on the right);

- Re-align electric lock MA7012.

- Press the RESET key on the electrical cabinet (if the unit has already been calibrated, the relative settings

will be deleted).

- Start up (or restart) the automation system as described in the section on start-up.

Содержание RODEO

Страница 1: ...IES RODEO AUTOMATION SYSTEM FOR SLIDING DOORS M71 rClY 3 1 0712000 CAME CANCELJ I AUTO na 19PM7iJ AUTOMATION SYSTEM FOR SLIDING DOORS WITH MICROPROCESSOR CONTROL _ for door wings weighting I up to 125kg each I ...

Страница 2: ...talled S M 2 Rl Normally open contact N O external sensor can be excluded S R2 2 R2 Normally open contact N O internal sensor Rl 2 M Normally open contact N O for step by step operation e 2 manual button I AI c Contact 1 2 and 2 C1 are normally closed N C and bridged together at the factory To use these functions replace the bridge connections with the relative devices The 2 el contact is used whe...

Страница 3: ...ess the mains power has been disconnected and the red power terminal has been removed from the emergency battery if installed ADJUSTMENT TRIMMERS IIUUU0 U111 MF9011 MF9111 10011 0 0 0 01 ttl V RALLAP ADJUSTMENTS TRIMMERS N 1 2 3 4 5 6 7 8 9 STAAT START BRA KI I PONT f AAClM SlCMtlO PONT Of INTENSITY IN SlOWDO FUCT1CN 9PENII K mAl TIC WN CLOSING SPEED OPENING SPEED ClOSIt G THE IN TW WN Sl MOO Otlf...

Страница 4: ...way SELECTION FUNCTIONS 1 ON Activation of spring loaded anti panic device set dip switch 4 to ON conslant push while dosing 1Q dip function selector see pag 19 2 Not used keep the dip in position OFF 3 ON Exdudes the photoelectric cell function MF9011 or MF9111 card inserted into the control board pag 22 4 Not used keep the dip in position OFF FUNCTIONS OF INDICATOR LED C0 CDCDCD CDCD tlE 1 2 3 4...

Страница 5: ...esired delay before automatic closing 9 Trimmer 2 can be adjusted only if function switch MA7041 has been installed and if this switch has been set to the partial opening position 10 Use the lever on the manual release system to re arm the electric lock if installed 0 If the automation system stops during the closing cycle the motor polarity may be incorrect If this occurs proceed as follows Disco...

Страница 6: ...71 SOLA MA7041 M19011 Mf9111 1I1111l11 23456 7 Note in case the MA 7041 selector is not connected and you wish to activate the antipanic function bond contacts 1 3 as shown in the figure Anti panic device with constant battery control Setting dip switch 2 of the 10 way module to the ON position on the interlock system set it on both panels activates the constant control of the battery charge buffe...

Страница 7: ...e unit locks on closure and is released electrically when the open command is given_ This is the default setting Locking with doors closed and open The unit locks both when open and closed when positioned correctly 1 and is released electrically by each open and close command Delayed locking The electric lock is unlocked when the first open command is given at initial start up or after a power fai...

Отзывы: